OpenGrowBox - Action Cycle Overview

Table of Contents

  1. VPD Perfection Mode
  2. VPD Target Mode
  3. Closed Environment Mode
  4. Safety Mechanisms
  5. Dynamic Fan Logic
  6. Deadband & Quiet Zone
  7. Dampening and Conflict Resolution
  8. Adaptive Cooldown
  9. Environment Guard Details

VPD Perfection Mode

Trigger

  • Event: VPDCreation (triggered by new sensor data)
  • Source: OGBVPDManager calculates VPD from Temperature + Humidity sensors

Action Flow

┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 1: VPD CALCULATION                                                      │
├─────────────────────────────────────────────────────────────────────────────┤
│ OGBVPDManager.calculateVPD()                                                │
│                                                                             │
│ • Calculates VPD from temperature and relative humidity                    │
│ • Stores: vpd.current, vpd.perfection, vpd.perfectMin, vpd.perfectMax     │
│ • Triggers: VPDCreation Event                                               │
└─────────────────────────────────────────────────────────────────────────────┘
                                      ↓
┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 2: MODE MANAGER                                                         │
├─────────────────────────────────────────────────────────────────────────────┤
│ OGBModeManager.handle_vpd_perfection()                                      │
│                                                                             │
│ 2.1 Reads VPD values:                                                       │
│     • currentVPD = data_store.getDeep("vpd.current")                        │
│     • perfectionVPD = data_store.getDeep("vpd.perfection")                  │
│     • perfectMinVPD = data_store.getDeep("vpd.perfectMin")                  │
│     • perfectMaxVPD = data_store.getDeep("vpd.perfectMax")                  │
│                                                                             │
 │ 2.2 🆕 SMART DEADBAND CHECK WITH HYSTERESIS (UPDATED!)                           │
 │     deadband = 0.05 (default)                                               │
 │     deviation = |currentVPD - perfectionVPD|                                │
 │     exit_threshold = deadband * 1.15 = 0.0575 (15% hysteresis)            │
 │                                                                             │
 │     IF deviation <= deadband:                                               │
 │       → _handle_smart_deadband() called                                     │
 │       → Climate devices reduced to minimum (10%-25%-50%)                    │
 │       → Air exchange devices (Exhaust, Intake, Window) reduced             │
 │       → Ventilation continues running                                      │
 │       → Hold time: 2.5 minutes                                              │
 │       → LogForClient with hysteresis info                                   │
 │       → RETURN (no VPD events!)                                             │
 │     ELIF deviation > exit_threshold:                                         │
 │       → Exit deadband (15% buffer to prevent oscillation)                   │
 │       → _reset_deadband_state()                                             │
 │       → Continue to Step 2.3                                                │
 │     ELSE:                                                                   │
 │       → Continue to Step 2.3                                                │
│                                                                             │
 │ 2.3 VPD Decision (only if outside deadband):                               │
 │     IF currentVPD < perfectMinVPD:                                          │
 │        → Emit: "increase_vpd"                                               │
 │     ELIF currentVPD > perfectMaxVPD:                                        │
 │        → Emit: "reduce_vpd"                                                 │
 │     ELSE:                                                                   │
 │        → NO ACTION (VPD within range)                                       │
 │        * FineTune REMOVED - Deadband handles this *                         │
└─────────────────────────────────────────────────────────────────────────────┘
                                     ↓
  ┌─────────────────────────────────────────────────────────────────────────────┐
  │ STEP 2: MODE MANAGER                                                       │
  ├─────────────────────────────────────────────────────────────────────────────┤
  │ OGBModeManager.handle_vpd_perfection()                                      │
  │                                                                             │
  │ Responsibility: Decide WHICH event to emit (no control logic)              │
  │                                                                             │
  │ Decision Logic:                                                             │
  │ • currentVPD < perfectMinVPD  → emit("increase_vpd")                      │
  │ • currentVPD > perfectMaxVPD  → emit("reduce_vpd")                          │
  │ • in Range                 → NO EVENT (handled by ActionManager)             │
  │                                                                             │
  │ Note: NO deadband check here - handled by ActionManager                     │
  └─────────────────────────────────────────────────────────────────────────────┘
                                      ↓
┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 3: ACTION MANAGER - DEADBAND CHECK 🎯                                  │
├─────────────────────────────────────────────────────────────────────────────┤
│ OGBActionManager.checkLimitsAndPublicate()                                  │
│                                                                             │
│ • Calls _is_vpd_in_deadband()                                               │
│ • Checks if currentVPD is within ±0.05 kPa of target                         │
│ • If in deadband: emit quiet zone signal and return (early exit)            │
│ • If NOT in deadband: continue to action processing                          │
│                                                                             │
│ This is the QUIET ZONE - devices pause when VPD is good!                   │
└─────────────────────────────────────────────────────────────────────────────┘
                                      ↓
┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 4: WEIGHTED DEVIATIONS CALCULATION (Central) 🎯                        │
├─────────────────────────────────────────────────────────────────────────────┤
│ OGBActionManager._calculate_weighted_deviations()                          │
│                                                                             │
│ • Calculates temp_weight, hum_weight (user- or plant-stage-specific)       │
│ • Calculates temp_deviation, hum_deviation                                   │
│ • Emit OGBWeightPublication (for all 3 modes!)                              │
│                                                                             │
│ Weighted deviations are used for Dampening and Cooldown                     │
└─────────────────────────────────────────────────────────────────────────────┘
                                      ↓
┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 5: VPD ACTIONS                                                         │
├─────────────────────────────────────────────────────────────────────────────┤
│ OGBVPDActions.increase_vpd() / reduce_vpd()                                 │
│                                                                             │
│ Creates Action Map based on Capabilities:                                   │
│ • canExhaust    → Increase/Reduce                                          │
│ • canIntake     → Reduce/Increase                                         │
│ • canVentilate  → Increase/Reduce                                          │
│ • canHumidify   → Reduce/Increase                                          │
│ • canDehumidify→ Increase/Reduce                                           │
│ • canHeat       → Increase/Reduce                                          │
│ • canCool       → Reduce/Increase                                          │
│ • canClimate    → Eval                                                     │
│ • canCO2        → Increase/Reduce (depending on light)                     │
│ • canLight      → Increase (if vpdLightControl=True)                       │
└─────────────────────────────────────────────────────────────────────────────┘
                                      ↓
┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 4: NIGHT HOLD CHECK 🌙                                                  │
├─────────────────────────────────────────────────────────────────────────────┤
│ OGBActionManager._check_vpd_night_hold()                                    │
│                                                                             │
│ IF light OFF AND nightVPDHold=False:                                        │
│   → _night_hold_fallback() is called                                        │
│                                                                             │
│   Night Hold Power-Saving Logic:                                            │
│   ┌─────────────────────────────────────────────────────────────────┐       │
│   │ Climate Devices (Save Power):                                   │       │
│   │ • canHeat       → Reduce  (Heater off)                         │       │
│   │ • canCool       → Reduce  (Cooler off)                         │       │
│   │ • canHumidify   → Reduce  (Humidifier off)                     │       │
│   │ • canDehumidify → Reduce  (Dehumidifier off)                   │       │
│   │ • canClimate    → Reduce  (Climate off)                        │       │
│   │ • canCO2        → Reduce  (CO2 off)                            │       │
│   │ • canLight      → Reduce  (Light off)                          │       │
│   └─────────────────────────────────────────────────────────────────┘       │
│   ┌─────────────────────────────────────────────────────────────────┐       │
│   │ Ventilation (Mold Prevention):                                  │       │
│   │ • canExhaust    → Increase  (Air exchange!)                    │       │
│   │ • canVentilate  → Increase  (Air circulation!)                 │       │
│   │ • canWindow     → Increase  (Air exchange!)                    │       │
│   │ • canIntake     → Variable  (based on outside temp)            │       │
│   │                                                                             │
│   │   Intake Logic:                                                              │
│   │   IF outside_temp >= (minTemp - 3°C):                                        │
│   │      → Increase (Outside air is warm enough)                                │
│   │   ELSE:                                                                      │
│   │      → Reduce (Too cold, save heating)                                      │
│   └─────────────────────────────────────────────────────────────────┘       │
│                                                                             │
│   Log: "NightHold: Power-Saving Mode - Climate minimized, Ventilation active"│
│                                                                             │
│ ELSE (light ON OR nightVPDHold=True):                                       │
│   → Continue to Step 6 (normal VPD processing)                              │
└─────────────────────────────────────────────────────────────────────────────┘
                                      ↓
┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 4: WEIGHTED DEVIATIONS CALCULATION (Central) 🎯                        │
├─────────────────────────────────────────────────────────────────────────────┤
│ OGBActionManager.checkLimitsAndPublicate()                                 │
│                                                                             │
│ • Calculates temp_weight, hum_weight (user- or plant-stage-specific)       │
│ • Calculates temp_deviation = (temp - min/max) * temp_weight               │
│ • Calculates hum_deviation = (hum - min/max) * hum_weight                  │
│ • Emit OGBWeightPublication (for all 3 modes!)                             │
│                                                                             │
│ Weighting Example:                                                          │
│ • humidity=2, temp=0 → Humidity error has 2x priority                     │
│ • humidity=0, temp=1 → Temperature error has 1x priority                   │
└─────────────────────────────────────────────────────────────────────────────┘
                                      ↓
┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 5: DAMPENING ACTIONS + DYNAMIC FAN LOGIC 🌡️                           │
├─────────────────────────────────────────────────────────────────────────────┤
│ OGBDampeningActions.process_actions_basic()                                │
│                                                                             │
│ • Receives temp_deviation, hum_deviation (from ActionManager)              │
│ • Applies Buffer Zones (prevents oscillation)                              │
│ • 🆕 DYNAMIC FAN LOGIC: Rewrites fan actions based on temperature!         │
│   - reduce_vpd + temp >= maxTemp - 1°C → exhaust INCREASE (cooling!)      │
│   - increase_vpd + temp <= minTemp + 1°C → exhaust REDUCE (heat retention)│
│   - Prevents critical situations when only one fan type is available       │
│ • Resolves Action conflicts (highest priority per capability)              │
│ • Filters through Dampening/Cooldown (uses weighted deviations)            │
│                                                                             │
│ IMPORTANT: Weighted Deviations are NOT recalculated!                       │
│ They are calculated centrally in ActionManager and used here.              │
└─────────────────────────────────────────────────────────────────────────────┘
                                     ↓
┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 6: PUBLICATION ACTION HANDLER                                          │
├─────────────────────────────────────────────────────────────────────────────┤
│ OGBActionManager.publicationActionHandler()                                 │
│                                                                             │
│ 7.1 Tent Mode Check: if Disabled → STOP                                   │
│                                                                             │
│ 7.2 🛡️ ENVIRONMENT GUARD APPLIED (STEP 8)                                   │
│                                                                             │
│ 7.3 Stores Actions for Analytics:                                          │
│     • previousActions (max 5)                                               │
│     • actionData (AI Training)                                              │
│                                                                             │
│ 7.4 Emit Device Events:                                                    │
│     canExhaust    → "Increase Exhaust" / "Reduce Exhaust"                 │
│     canIntake     → "Increase Intake" / "Reduce Intake"                    │
│     canVentilate  → "Increase Ventilation" / "Reduce Ventilation"         │
│     canHeat       → "Increase Heater" / "Reduce Heater"                   │
│     canCool       → "Increase Cooler" / "Reduce Cooler"                    │
│     ...                                                                   │
└─────────────────────────────────────────────────────────────────────────────┘
                                     ↓
┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 7: ENVIRONMENT GUARD 🛡️ (Detailed)                                    │
├─────────────────────────────────────────────────────────────────────────────┤
│ OGBActionManager._apply_environment_guard()                                │
│ OGBEnvironmentGuard.evaluate_environment_guard()                           │
│                                                                             │
│ ONLY FOR: canExhaust, canIntake WITH Increase                               │
│ (Note: canVentilate is NOT handled by EnvironmentGuard -                   │
│       internal air circulation, no air exchange with outside)               │
│ 1. SELECT AIR SOURCE:                                                      │
│    • Intake → Outsite (Weather data) if available                          │
│    • Exhaust → Ambient (Room data)                                         │
│                                                                             │
│ 2. EVALUATE RISKS:                                                         │
│    • temp_risk: Too cold inside + source even colder                       │
│    • humidity_risk: Too dry + source even drier                            │
│    • temp_benefit: Too cold + source warmer                                │
│    • humidity_benefit: Too wet + source drier                              │
│    • humidity_critical: humidity >= maxHumidity (MOLD RISK!)               │
│    • humidity_critical_dry: humidity <= minHumidity (TOO DRY!)             │
│                                                                             │
│ 3. PRIORITY DECISION:                                                      │
│    1️⃣ humidity_critical → ALLOW (Emergency override!)                      │
│    2️⃣ humidity_critical_dry → ALLOW (Emergency override!)                  │
│    3️⃣ humidity_benefit → ALLOW (Drying needed)                             │
│    4️⃣ temp_benefit → ALLOW (Heating needed)                                │
│    5️⃣ temp_risk → BLOCK (Too cold!)                                       │
│    6️⃣ humidity_risk → BLOCK (Too dry!)                                     │
│    7️⃣ No risk → ALLOW                                                      │
│                                                                             │
│ 4. RESULT:                                                                 │
│    BLOCKED → Action "Increase" → "Reduce" rewritten                        │
│    ALLOWED → Action remains unchanged                                      │
│                                                                             │
│ 5. LOG FOR CLIENT:                                                         │
│    • On Block: WARNING with detailed info                                  │
│    • On Allow: DEBUG                                                       │
└─────────────────────────────────────────────────────────────────────────────┘
                                     ↓
┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 8: DEVICE EXECUTION                                                    │
├─────────────────────────────────────────────────────────────────────────────┤
│ Device-specific on() handlers receive events:                              │
│                                                                             │
│ • Exhaust.on("Increase Exhaust") → increaseAction()                       │
│ • Intake.on("Increase Intake") → increaseAction()                         │
│ • Heater.on("Increase Heater") → increaseAction()                         │
│                                                                             │
│ IMPORTANT: Device.should_block_air_exchange_increase() also checks         │
│ EnvironmentGuard (for direct Increase-Actions)!                            │
└─────────────────────────────────────────────────────────────────────────────┘

VPD Target Mode

Differences to VPD Perfection

Aspect VPD Perfection VPD Target
VPD Calculation Compares with perfectMin/max Compares with targetedMin/Max
Event Names increase_vpd, reduce_vpd vpdt_increase_vpd, vpdt_reduce_vpd
VPD Actions increase_vpd() increase_vpd_target()
Handler _handle_increase_vpd() _handle_vpdt_increase_vpd()
Deviation Temp/Hum weighted (Plant Stage) Only VPD Deviation (Current - Target)
Dampening process_actions_basic() process_actions_target_basic()
WeightPublication ✅ Emitted ❌ Not emitted (only VPD deviation)

Action Flow (identical to VPD Perfection except Step 3)

┌─────────────────────────────────────────────────────────────────────────────┐
│ DIFFERENCES:                                                                │
├─────────────────────────────────────────────────────────────────────────────┤
│                                                                             │
│ STEP 3: handle_targeted_vpd()                                              │
│ • Reads: vpd.targeted, vpd.targetedMin, vpd.targetedMax, vpd.tolerance     │
│ • Calculates: min_vpd = targeted - (targeted * tolerance/100)               │
│              max_vpd = targeted + (targeted * tolerance/100)               │
│                                                                             │
 │ • 🆕 SMART DEADBAND CHECK WITH HYSTERESIS (UPDATED!):                              │
 │   deadband = 0.05 (default)                                                 │
 │   deviation = |currentVPD - targetedVPD|                                    │
 │   exit_threshold = deadband * 1.15 = 0.0575 (15% hysteresis)                │
 │                                                                             │
 │   IF deviation <= deadband:                                                 │
 │     → _handle_smart_deadband() called                                       │
 │     → Climate devices reduced to minimum (10%-25%-50%)                      │
 │     → Air exchange devices (Exhaust, Intake, Window) reduced               │
 │     → Ventilation continues running                                        │
 │     → Hold time: 2.5 minutes                                                │
 │     → LogForClient with hysteresis info                                     │
 │     → RETURN (no VPD events!)                                               │
 │   ELIF deviation > exit_threshold:                                           │
 │     → Exit deadband (15% buffer to prevent oscillation)                     │
 │     → _reset_deadband_state()                                               │
 │                                                                             │
│                                                                             │
│ • Decision (only if outside deadband):                                      │
│   IF currentVPD < min_vpd:                                                  │
│      → Emit: "vpdt_increase_vpd"                                            │
│   ELIF currentVPD > max_vpd:                                                │
│      → Emit: "vpdt_reduce_vpd"                                              │
│                                                                             │
│ STEP 4: VPD DEVIATION ONLY (NEW!)                                          │
│ • checkLimitsAndPublicateTarget() calculates ONLY VPD Deviation:           │
│   vpd_deviation = currentVPD - targetVPD                                    │
│                                                                             │
│   ❌ NO Temp/Hum weighted deviations!                                       │
│   ❌ NO Plant Stage Limits!                                                 │
│   ✅ ONLY VPD-based!                                                        │
│                                                                             │
│   Example:                                                                  │
│   • currentVPD = 0.62 kPa                                                   │
│   • targetVPD = 1.20 kPa                                                    │
│   • vpd_deviation = -0.58 kPa                                               │
│                                                                             │
│   LogForClient contains:                                                    │
│   • "vpdDeviation": -0.58                                                   │
│   • "currentVPD": 0.62                                                      │
│   • "targetVPD": 1.20                                                       │
│                                                                             │
│ • No Dampening-Weighted Deviations (only VPD-based)                        │
│                                                                             │
│ ALL OTHER STEPS ARE IDENTICAL!                                              │
│ • Conflict Resolution (Step 4)                                             │
│ • Dampening Actions (Step 5)                                               │
│ • Night Hold Check (Step 3)                                                │
│ • Environment Guard (Step 7)                                                │
│ • Device Execution (Step 8)                                                │
└─────────────────────────────────────────────────────────────────────────────┘

Closed Environment Mode

Overview

Closed Environment mode is designed for recirculating systems in sealed chambers where temperature and humidity control is critical.

Key Characteristics:

  • Control Targets: Uses tentData.minTemp, tentData.maxTemp, tentData.minHumidity, tentData.maxHumidity (ALWAYS filled)
  • Data Source: tentData is ALWAYS filled with either:
    • Plant-stage-specific min/max values (from plantStages config)
    • OR user-defined min/max values (from UI)
  • Control Logic: Maintains temperature and humidity within min/max limits
  • VPD Usage: VPD is ONLY used for Smart Deadband (informational, NOT for control)
  • Night Mode: Power-saving mode when light OFF and nightVPDHold=False
  • Purpose: Optimized for recirculating systems where ambient exchange is minimal

Differences to VPD Perfection

Aspect VPD Perfection Closed Environment
Mode Handler handle_vpd_perfection() handle_closed_environment()
Manager OGBModeManager → ClosedEnvironmentManager
Action Handler ClosedActions.execute_closed_environment_cycle()
Night Hold ✅ Active ✅ Active (Power-Saving Mode)
VPD Usage ✅ Primary control target ⚠️ Only for Smart Deadband (NOT for control)
Control Targets VPD-based (perfectMin/max) tentData min/max (ALWAYS filled)
Data Source vpd.perfection (calculated) tentData.min/max (from UI or plantStages)
Weighted Deviations ✅ Central calculation ✅ Central calculation (0,0,0,0)
WeightPublication ✅ Emitted ✅ Emitted
Environment Guard ✅ Active ✅ Active
checkLimitsAndPublicate checkLimitsAndPublicate() checkLimitsAndPublicateNoVPD()
CO2 Control in Deadband ❌ No (only outside deadband) ✅ Yes (important for sealed chambers)
Device State Restoration ✅ Yes (restoreFromMinimum) ✅ Yes (restoreFromMinimum)

Control Logic (How It Works)

┌─────────────────────────────────────────────────────────────────────────────┐
│ CLOSED ENVIRONMENT CONTROL LOGIC                                         │
├─────────────────────────────────────────────────────────────────────────────┤
│                                                                             │
│  DATA SOURCE (ALWAYS FILLED):                                             │
│  ├─ tentData.minTemp  ← User-defined OR plant-stage-specific           │
│  ├─ tentData.maxTemp  ← User-defined OR plant-stage-specific           │
│  ├─ tentData.minHumidity  ← User-defined OR plant-stage-specific       │
│  └─ tentData.maxHumidity  ← User-defined OR plant-stage-specific       │
│                                                                             │
│  CONTROL DECISION:                                                           │
│  IF currentTemp < minTemp:                                               │
│    → Heat until minTemp reached                                           │
│  ELIF currentTemp > maxTemp:                                             │
│    → Cool until maxTemp reached                                           │
│  ELSE:                                                                     │
│    → No action (temperature in range)                                      │
│                                                                             │
│  IF currentHumidity < minHumidity:                                       │
│    → Humidify until minHumidity reached                                   │
│  ELIF currentHumidity > maxHumidity:                                     │
│    → Dehumidify until maxHumidity reached                                 │
│  ELSE:                                                                     │
│    → No action (humidity in range)                                        │
│                                                                             │
│  VPD IS ONLY USED FOR:                                                     │
│  • Smart Deadband check (informational)                                   │
│  • Logging/display purposes                                                │
│  • NOT for control decisions!                                             │
│                                                                             │
└─────────────────────────────────────────────────────────────────────────────┘

Example: Late Flower Scenario

User Configuration:
┌─────────────────────────────────────────────────────────────────────────┐
│ tentData.minTemp:      20.0°C (from user UI)                         │
│ tentData.maxTemp:      28.0°C (from user UI)                         │
│ tentData.minHumidity:  40.0% (from user UI)                         │
│ tentData.maxHumidity:  60.0% (from user UI)                         │
└─────────────────────────────────────────────────────────────────────────┘

Control Behavior:
┌─────────────────────────────────────────────────────────────────────────┐
│ Current: 25.5°C / 58% RH                                                │
│                                                                          │
│ Temperature:                                                            │
│   • 25.5°C is within 20.0-28.0°C range → NO ACTION                 │
│                                                                          │
│ Humidity:                                                              │
│   • 58% is within 40-60% range → NO ACTION                            │
│                                                                          │
│ VPD (informational):                                                    │
│   • VPD = 1.05 kPa (calculated from T/H, NOT used for control)        │
│   • vpdCurrent displayed in logs for monitoring only                   │
└─────────────────────────────────────────────────────────────────────────┘

Action Flow

┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 1: MODE MANAGER                                                       │
├─────────────────────────────────────────────────────────────────────────────┤
│ OGBModeManager.handle_closed_environment()                                │
│                                                                             │
  │ 1.0 🆕 NIGHT MODE CHECK (NEW!)                                            │
  │     is_light_on = data_store.getDeep("isPlantDay.islightON")             │
  │     night_vpd_hold = data_store.getDeep("controlOptions.nightVPDHold")   │
  │                                                                             │
  │     IF NOT is_light_on AND NOT night_vpd_hold:                            │
  │       → Night Mode Power-Saving is handled in Step 2                      │
  │       → Continue to Step 1.1                                               │
  │                                                                             │
  │ 1.1 🆕 SMART DEADBAND CHECK WITH HYSTERIS (VPD-based)                   │
  │     currentVPD = data_store.getDeep("vpd.current")                        │
  │     targetVPD = data_store.getDeep("vpd.targeted") or vpd.perfection     │
  │                                                                             │
  │     IF currentVPD is not None AND targetVPD is not None:                   │
  │       deadband = 0.05 (default)                                            │
  │       deviation = |currentVPD - targetVPD|                                 │
  │       exit_threshold = deadband * 1.15 = 0.0575 (15% hysteresis)           │
  │                                                                             │
  │       IF deviation <= deadband:                                            │
  │         → deadband_active = _handle_smart_deadband() returns bool        │
  │                                                                             │
  │         IF deadband_active == True:                                        │
  │           → Climate devices reduced to minimum (10%-25%-50%)               │
  │           → Air exchange devices (Exhaust, Intake, Window) reduced        │
  │           → Ventilation continues running                                 │
  │           → Hold time: 2.5 minutes                                        │
  │           → LogForClient with hysteresis info                             │
  │           → CO2 Control still executed (important!)                       │
  │           → RETURN (no normal Closed Env Actions!)                         │
  │         ELSE (deadband_active == False):                                   │
  │           → Deadband blocked (e.g., night mode without nightVPDHold)       │
  │           → Continue to Step 1.2                                           │
  │       ELIF deviation > exit_threshold:                                     │
  │         → Exit deadband (15% buffer to prevent oscillation)                │
  │         → _reset_deadband_state()                                          │
  │                                                                             │
  │ 1.2 Normal Closed Environment Cycle:                                      │
  │     → ClosedEnvironmentManager.execute_cycle()                            │
└─────────────────────────────────────────────────────────────────────────────┘
                                      ↓
┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 2: CLOSED ACTIONS                                                      │
├─────────────────────────────────────────────────────────────────────────────┤
│ ClosedActions.execute_closed_environment_cycle()                           │
│                                                                             │
│ 2.0 🆕 NIGHT MODE POWER-SAVING (NEW!)                                       │
│     is_light_on = dataStore.getDeep("isPlantDay.islightON")                 │
│     night_vpd_hold = dataStore.getDeep("controlOptions.nightVPDHold")      │
│                                                                             │
│     IF NOT is_light_on AND NOT night_vpd_hold:                              │
│       → _handle_night_mode_power_saving() called                            │
│                                                                             │
│       Night Mode Power-Saving Logic:                                        │
│       ┌─────────────────────────────────────────────────────────────────┐   │
│       │ Climate Devices (Save Power):                                   │   │
│       │ • canHeat, canCool, canHumidify, canDehumidify → Reduce (OFF) │   │
│       │ • canClimate, canCO2, canLight → Reduce (OFF)                   │   │
│       └─────────────────────────────────────────────────────────────────┘   │
│       ┌─────────────────────────────────────────────────────────────────┐   │
│       │ Ventilation (Mold Prevention):                                  │   │
│       │ • canExhaust, canVentilate, canWindow → Increase               │   │
│       │ • canIntake → Variable (based on outside temp)                  │
│       └─────────────────────────────────────────────────────────────────┘   │
│                                                                             │
│       → LogForClient with isNightMode=True, nightVPDHold=False             │
│       → RETURN (no normal Closed Env Actions!)                              │
│                                                                             │
│ 2.1 NOTE: Smart Deadband (VPD-based) DEAKTIVIERT für Closed Environment │
│     → Closed Environment uses ONLY temp/hum deadbands (NOT VPD-based)        │
│                                                                             │
│ 2.2 Check Closed Environment specific deadbands (Temp and Humidity):       │
│     closed_db_status = await _check_closed_deadbands()                      │
│     temp_in_db = closed_db_status["temp_in_deadband"]                       │
│     hum_in_db = closed_db_status["hum_in_deadband"]                         │
│     temp_dev = closed_db_status["temp_deviation"]                           │
│     hum_dev = closed_db_status["hum_deviation"]                             │
│     temp_target = closed_db_status["temp_target"]  ← (min + max) / 2      │
│     hum_target = closed_db_status["hum_target"]    ← (min + max) / 2      │
│                                                                             │
│ 2.3 Collect all actions:                                                    │
│     • o2_actions = monitor_o2_safety()                                     │
│     • co2_actions = maintain_co2()                                          │
│     • temp_actions = control_temperature_closed() (if NOT in temp db)      │
│     • hum_actions = control_humidity_closed() (if NOT in hum db)           │
│     • air_actions = optimize_air_recirculation() (if NOT in any db)        │
│                                                                             │
│     NOTE: All actions are collected and executed in ONE batch!             │
└─────────────────────────────────────────────────────────────────────────────┘
                                      ↓
┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 3: TEMPERATURE/HUMIDITY CONTROL                                       │
├─────────────────────────────────────────────────────────────────────────────┤
│ ClosedActions.control_temperature_closed()                                 │
│ ClosedActions.control_humidity_closed()                                    │
│                                                                             │
│ Uses: _increase_temperature() / _decrease_temperature()                   │
│       _increase_humidity() / _decrease_humidity()                         │
│                                                                             │
│ Each method returns action_map (does NOT execute immediately!)             │
│ Actions are collected for batch execution                                  │
│                                                                             │
│ IMPORTANT: Uses tentData min/max limits for control                        │
│ • Control Logic: current vs min/max (NOT VPD targets!)                  │
│ • temp_target in log = (minTemp + maxTemp) / 2 (for display only)          │
│ • hum_target in log = (minHumidity + maxHumidity) / 2 (for display only)    │
└─────────────────────────────────────────────────────────────────────────────┘
                                      ↓
┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 4: BATCH EXECUTION                                                     │
├─────────────────────────────────────────────────────────────────────────────┤
│ ClosedActions.execute_closed_environment_cycle()                           │
│                                                                             │
│ All actions combined into single action_map                                │
│ → action_manager.checkLimitsAndPublicateNoVPD(all_actions)                 │
│                                                                             │
│ Single LogForClient Event:                                                  │
│ {                                                                           │
│   "Name": "dev_room",                                                       │
│   "message": "Closed Environment: 5 actions executed",                     │
│   "actions": "canExhaust:Increase, canCool:Reduce, canDehumidify:Increase",│
│   "actionCount": 5,                                                         │
│   "tempDeviation": 1.6,                                                     │
│   "humDeviation": 0.8,                                                      │
│   "tempCurrent": 25.5,                                                      │
│   "tempTarget": 24.0,  ⚠️ (minTemp + maxTemp) / 2, NOT VPD target!          │
│   "humCurrent": 58.0,                                                       │
│   "humTarget": 50.0,   ⚠️ (minHumidity + maxHumidity) / 2, NOT VPD target!  │
│   "vpdCurrent": 1.05,  ⚠️ For informational purposes only (NOT used for control)│
│   "smartDeadbandActive": false                                              │
│ }                                                                           │
└─────────────────────────────────────────────────────────────────────────────┘
                                      ↓
┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 2: CLOSED ACTIONS                                                      │
├─────────────────────────────────────────────────────────────────────────────┤
│ ClosedActions.execute_closed_environment_cycle()                           │
│                                                                             │
│ 2.0 🆕 NIGHT MODE POWER-SAVING (NEW!)                                       │
│     is_light_on = dataStore.getDeep("isPlantDay.islightON")                 │
│     night_vpd_hold = dataStore.getDeep("controlOptions.nightVPDHold")      │
│                                                                             │
│     IF NOT is_light_on AND NOT night_vpd_hold:                              │
│       → _handle_night_mode_power_saving() called                            │
│                                                                             │
│       Night Mode Power-Saving Logic:                                        │
│       ┌─────────────────────────────────────────────────────────────────┐   │
│       │ Climate Devices (Save Power):                                   │   │
│       │ • canHeat, canCool, canHumidify, canDehumidify → Reduce (OFF) │   │
│       │ • canClimate, canCO2, canLight → Reduce (OFF)                   │   │
│       └─────────────────────────────────────────────────────────────────┘   │
│       ┌─────────────────────────────────────────────────────────────────┐   │
│       │ Ventilation (Mold Prevention):                                  │   │
│       │ • canExhaust, canVentilate, canWindow → Increase               │   │
│       │ • canIntake → Variable (based on outside temp)                  │   │
│       └─────────────────────────────────────────────────────────────────┘   │
│                                                                             │
│       → LogForClient with isNightMode=True, nightVPDHold=False             │
│       → RETURN (no normal Closed Env Actions!)                              │
│                                                                             │
│ 2.1 NOTE: Smart Deadband (VPD-based) DEAKTIVIERT für Closed Environment │
│     → Closed Environment uses ONLY temp/hum deadbands (NOT VPD-based)        │
│                                                                             │
│ 2.2 Check Closed Environment specific deadbands (Temp and Humidity):       │
│     closed_db_status = await _check_closed_deadbands()                      │
│     temp_in_db = closed_db_status["temp_in_deadband"]                       │
│     hum_in_db = closed_db_status["hum_in_deadband"]                         │
│     temp_dev = closed_db_status["temp_deviation"]                           │
│     hum_dev = closed_db_status["hum_deviation"]                             │
│     temp_target = closed_db_status["temp_target"]  ⚠️ OWN TARGET, NOT VPD! │
│     hum_target = closed_db_status["hum_target"]    ⚠️ OWN TARGET, NOT VPD! │
│                                                                             │
│ 2.3 Collect all actions:                                                    │
│     • o2_actions = monitor_o2_safety()                                     │
│     • co2_actions = maintain_co2()                                          │
│     • temp_actions = control_temperature_closed() (if NOT in temp db)      │
│     • hum_actions = control_humidity_closed() (if NOT in hum db)           │
│     • air_actions = optimize_air_recirculation() (if NOT in any db)        │
│                                                                             │
│     NOTE: All actions are collected and executed in ONE batch!             │
└─────────────────────────────────────────────────────────────────────────────┘
                                      ↓
┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 3: TEMPERATURE/HUMIDITY CONTROL                                       │
├─────────────────────────────────────────────────────────────────────────────┤
│ ClosedActions.control_temperature_closed()                                 │
│ ClosedActions.control_humidity_closed()                                    │
│                                                                             │
│ Uses: _increase_temperature() / _decrease_temperature()                   │
│       _increase_humidity() / _decrease_humidity()                         │
│                                                                             │
│ Each method returns action_map (does NOT execute immediately!)             │
│ Actions are collected for batch execution                                  │
│                                                                             │
│ IMPORTANT: Uses OWN temp/hum targets, NOT VPD targets!                    │
│ • temp_target = await _get_reference_temperature_target()                   │
│ • hum_target = await _get_reference_humidity_target()                      │
└─────────────────────────────────────────────────────────────────────────────┘
                                      ↓
┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 4: BATCH EXECUTION                                                     │
├─────────────────────────────────────────────────────────────────────────────┤
│ ClosedActions.execute_closed_environment_cycle()                           │
│                                                                             │
│ All actions combined into single action_map                                │
│ → action_manager.checkLimitsAndPublicateNoVPD(all_actions)                 │
│                                                                             │
│ Single LogForClient Event:                                                  │
│ {                                                                           │
│   "Name": "dev_room",                                                       │
│   "message": "Closed Environment: 5 actions executed",                     │
│   "actions": "canExhaust:Increase, canCool:Reduce, canDehumidify:Increase",│
│   "actionCount": 5,                                                         │
│   "tempDeviation": 1.6,                                                     │
│   "humDeviation": 0.8,                                                      │
│   "co2Status": "anheben",                                                   │
│   "tempStatus": "kuehlen",                                                  │
│   "humStatus": "entfeuchten",                                               │
│   "tempCurrent": 24.5,                                                      │
│   "tempTarget": 26.0,  ⚠️ OWN TARGET, NOT VPD TARGET!                     │
│   "humCurrent": 58.0,                                                       │
│   "humTarget": 60.0,   ⚠️ OWN TARGET, NOT VPD TARGET!                     │
│   "co2Current": 750,                                                        │
│   "co2TargetMin": 800,                                                      │
│   "co2TargetMax": 1500,                                                     │
│   "vpdCurrent": 1.05,  ⚠️ For informational purposes only!               │
│   "smartDeadbandActive": false                                              │
│ }                                                                           │
└─────────────────────────────────────────────────────────────────────────────┘
                                      ↓
┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 5: CONFLICT RESOLUTION & ENVIRONMENT GUARD                            │
├─────────────────────────────────────────────────────────────────────────────┤
│ OGBActionManager.checkLimitsAndPublicateNoVPD()                            │
│                                                                             │
│ • Resolve action conflicts                                                  │
│ • Apply Environment Guard                                                   │
│ • Execute actions                                                           │
│                                                                             │
│ NOTE: No Core VPD Logic (Buffer Zones, VPD Context, Deviations)           │
│       Closed Environment has its own control logic!                        │
└─────────────────────────────────────────────────────────────────────────────┘
                                      ↓
┌─────────────────────────────────────────────────────────────────────────────┐
│ STEP 6: DEVICE EXECUTION                                                    │
├─────────────────────────────────────────────────────────────────────────────┤
│ ✅ IDENTICAL TO VPD PERFECTION                                              │
└─────────────────────────────────────────────────────────────────────────────┘

Safety Mechanisms

Overview

Safety VPD Perf VPD Target Closed Env
Night Hold ✅ (Power-Saving Mode) ✅ (Power-Saving Mode) ✅ (Power-Saving Mode - NEW!)
Smart Deadband ✅ (with 15% hysteresis, climate reduced, air exchange reduced) ✅ (with 15% hysteresis, climate reduced, air exchange reduced) ✅ (VPD-based, with 15% hysteresis, returns bool)
Dynamic Fan Logic ✅ (Temperature-aware fan control) ✅ (Temperature-aware fan control) ❌
Humidity Critical Override ✅ ✅ ✅
Environment Guard ✅ (optional) ✅ (optional) ✅ (optional)
Buffer Zones ✅ ✅ ✅
Conflict Resolution ✅ ✅ ✅
Weighted Deviations ✅ ✅ ✅ (all 0)
Dampening/Cooldown ✅ (optional) ✅ (optional) ❌

Dynamic Fan Logic (Temperature-Aware Fan Control)

Problem: Static VPD fan logic can be dangerous when users only have one fan type (e.g., only exhaust, no intake).

Solution: _apply_dynamic_fan_logic() rewrites fan actions based on temperature priorities.

How It Works

┌─────────────────────────────────────────────────────────────────────────────┐
│ DYNAMIC FAN LOGIC FLOW                                                      │
├─────────────────────────────────────────────────────────────────────────────┤
│                                                                             │
│  reduce_vpd context (VPD too high):                                        │
│  ┌─────────────────────────────────────────────────────────────────────┐   │
│  │ IF temp >= maxTemp - 1°C:                                           │   │
│  │   → canExhaust: Reduce → INCREASE (cool instead of trap heat)      │   │
│  │   → canVentilate: Reduce → INCREASE                                │   │
│  │   → canIntake: Increase (unchanged - helps cooling)                │   │
│  │ ELSE:                                                               │   │
│  │   → Classic behavior (Reduce exhaust, Increase intake)             │   │
│  └─────────────────────────────────────────────────────────────────────┘   │
│                                                                             │
│  increase_vpd context (VPD too low):                                       │
│  ┌─────────────────────────────────────────────────────────────────────┐   │
│  │ IF temp <= minTemp + 1°C:                                           │   │
│  │   → canExhaust: Increase → REDUCE (retain heat)                    │   │
│  │   → canVentilate: Increase → REDUCE                                │   │
│  │   → canIntake: Reduce (unchanged - helps retain heat)              │   │
│  │ ELSE:                                                               │   │
│  │   → Classic behavior (Increase exhaust, Reduce intake)             │   │
│  └─────────────────────────────────────────────────────────────────────┘   │
│                                                                             │
│  FAN_TEMP_BUFFER = 1.0°C (prevents oscillation near limits)                │
└─────────────────────────────────────────────────────────────────────────────┘

Decision Matrix

Context Temperature canExhaust canIntake canVentilate Reason
reduce_vpd temp >= maxTemp - 1°C Increase Increase Increase Cooling priority
reduce_vpd temp < maxTemp - 1°C Reduce Increase Reduce Classic VPD-reduce
increase_vpd temp <= minTemp + 1°C Reduce Reduce Reduce Heat retention priority
increase_vpd temp > minTemp + 1°C Increase Reduce Increase Classic VPD-increase

Example Scenarios

Scenario 1: Critical - only exhaust, high temp, VPD too high

User has: canExhaust only (no intake)
VPD: Too high → reduce_vpd triggered
Temperature: 27.5°C (maxTemp = 28°C)

Before Dynamic Fan Logic:
  → canExhaust: Reduce (traps heat! DANGER!)

After Dynamic Fan Logic:
  → canExhaust: Increase (cooling! SAFE!)
  
Log: "DynamicFan: temp 27.5°C >= 27.0°C, exhaust INCREASED for cooling"

Scenario 2: Critical - only exhaust, low temp, VPD too low

User has: canExhaust only (no intake)
VPD: Too low → increase_vpd triggered
Temperature: 20.5°C (minTemp = 20°C)

Before Dynamic Fan Logic:
  → canExhaust: Increase (sucks out heat! DANGER!)

After Dynamic Fan Logic:
  → canExhaust: Reduce (retains heat! SAFE!)
  
Log: "DynamicFan: temp 20.5°C <= 21.0°C, exhaust REDUCED to retain heat"

Scenario 3: Both fans available, temp OK

User has: canExhaust + canIntake
VPD: Too high → reduce_vpd triggered
Temperature: 24°C (minTemp = 20°C, maxTemp = 28°C)

Dynamic Fan Logic: No changes (temp in safe range)
  → canExhaust: Reduce (classic behavior)
  → canIntake: Increase (classic behavior)

Implementation

Location: OGBDampeningActions._apply_dynamic_fan_logic()

Integration Points:

  • _enhance_action_map() - Main path for Core VPD Logic
  • process_actions_basic() - Deprecated but still used
  • process_actions_target_basic() - VPD Target mode

Code:

def _apply_dynamic_fan_logic(self, action_map: List, tent_data: Dict) -> List:
    """Rewrite fan actions based on temperature priorities."""
    
    current_temp = tent_data.get("temperature")
    max_temp = tent_data.get("maxTemp")
    min_temp = tent_data.get("minTemp")
    
    # Detect VPD context
    is_reduce_vpd = any(a.capability == 'canExhaust' and a.action == 'Reduce' 
                        for a in action_map)
    is_increase_vpd = any(a.capability == 'canExhaust' and a.action == 'Increase' 
                          for a in action_map)
    
    FAN_TEMP_BUFFER = 1.0  # 1°C buffer
    
    for action in action_map:
        cap = action.capability
        act = action.action
        
        # reduce_vpd + high temp → INCREASE exhaust/ventilation
        if is_reduce_vpd and current_temp >= (max_temp - FAN_TEMP_BUFFER):
            if cap in ('canExhaust', 'canVentilate') and act == 'Reduce':
                action.action = 'Increase'
                action.message += " [DynamicFan: cooling priority]"
        
        # increase_vpd + low temp → REDUCE exhaust/ventilation
        elif is_increase_vpd and current_temp <= (min_temp + FAN_TEMP_BUFFER):
            if cap in ('canExhaust', 'canVentilate') and act == 'Increase':
                action.action = 'Reduce'
                action.message += " [DynamicFan: heat retention priority]"
    
    return action_map

Why This Matters

  • Single-fan setups (exhaust-only) are common in budget grows
  • Static VPD logic assumes both exhaust AND intake are available
  • Without dynamic correction:
    • High-VPD + high-temp + reduce exhaust = heat trap → plant stress/death
    • Low-VPD + low-temp + increase exhaust = heat loss → plant stress/death
  • The 1°C buffer prevents rapid oscillation near temperature limits

Test Coverage

Comprehensive test suite in tests/logic/actions/test_dynamic_fan_logic.py:

  • ✅ reduce_vpd + temp OK + both fans → unchanged
  • ✅ reduce_vpd + temp HIGH + only exhaust → switches to Increase
  • ✅ reduce_vpd + temp HIGH + both fans → exhaust switches to Increase
  • ✅ increase_vpd + temp OK + only exhaust → unchanged
  • ✅ increase_vpd + temp LOW + only exhaust → switches to Reduce
  • ✅ increase_vpd + temp LOW + both fans → both reduce
  • ✅ reduce_vpd + temp HIGH + ventilation → also switches
  • ✅ No fan actions → pass-through unchanged
  • ✅ Missing tent_data → pass-through unchanged

Smart Deadband (Advanced)

The Smart Deadband has been enhanced with dynamic behavior, predictive logic, and energy-saving features.

Disabling the Smart Deadband: Setting the VPD deadband entity (OGB_VPDDeadband_* → controlOptionData.deadband.vpdDeadband) to 0.0 kPa turns the Smart Deadband off. All three gate sites treat a deadband <= 0 as disabled, so VPD Perfection and VPD Target run full regulation even when current is exactly at target. Negative values are clamped to 0.0 by the setter.

Dynamic Deadband Based on Plant Stage (VPD Perfection only)

# Plant stage specific deadband values:
stage_deadbands = {
    "Germination": 0.03,  # Very sensitive phase
    "Clones": 0.03,       # Very sensitive phase
    "EarlyVeg": 0.05,     # Normal
    "MidVeg": 0.05,       # Normal
    "LateVeg": 0.04,      # More precise (transition to flower)
    "EarlyFlower": 0.04,  # More precise
    "MidFlower": 0.05,    # Normal
    "LateFlower": 0.05,   # Normal
}

Why different deadbands?

  • Sensitive phases (Germination/Clones): Tighter control (±0.03 kPa)
  • Transition phases (LateVeg/EarlyFlower): More precise (±0.04 kPa)
  • Stable phases (MidVeg/MidFlower/LateFlower): Standard control (±0.05 kPa)

3-Stage Gradual Reduction

Instead of immediately reducing all devices to minimum, the Smart Deadband now uses gradual reduction based on VPD stability:

Stage VPD Deviation Climate Devices Air-Exchange Devices Description
Stage 1 (Soft) 0.02-0.04 kPa 50% 75% Slight reduction, VPD close to target
Stage 2 (Medium) 0.04-0.05 kPa 25% 50% Moderate reduction, VPD in deadband
Stage 3 (Full) Stable 2+ min 10% 25% Maximum reduction, VPD stable

Benefits:

  • ✅ Faster response when VPD changes (not everything at minimum)
  • ✅ Less oscillation (gradual changes)
  • ✅ Better energy saving (only reduce what's needed)

Deadband Correction Actions

Reducing every device to minimum is not always correct. If a value is outside its physical band while the VPD sits inside the deadband, the device that corrects that value must be pushed back up — otherwise the deadband silently freezes the room at an unsafe temperature or humidity.

Which devices get a correction

Corrections are only generated in the direction the device actually corrects:

Condition Devices activated
temperature > maxTemp Cooler, Exhaust
temperature < minTemp Heater
humidity > maxHumidity Dehumidifier
humidity < minHumidity Humidifier

Because a correction device is only ever added when the value is too low for it (too cold for a heater, too dry for a humidifier), every correction action is an Increase. The duty cycle is derived from the deviation (30 % / 50 % / 70 %).

Note: Heater and Humidifier previously mapped to Reduce here, which switched an under-temperature heater and an under-humidity humidifier off — exactly the wrong direction. They now correctly map to Increase.

Passing corrections through the action chain

checkLimitsAndPublicate() normally re-evaluates the VPD deadband and returns early (emitting the quiet-zone idle event) whenever the VPD is inside the deadband. Corrections are produced because the VPD is inside the deadband, so that check would discard precisely the actions it created.

The deadband correction paths therefore call:

await self.action_manager.checkLimitsAndPublicate(
    correction_actions, from_deadband_correction=True
)

The flag only skips the deadband early-return; night-hold, dampening/cooldown, environment guard and device execution still run. All other callers keep the default (False) and are unaffected.

Predictive Behavior with Trend Analysis

The Smart Deadband analyzes the last 3 VPD values to predict future behavior:

def _calculate_trend(current_vpd: float) -> str:
    # Returns: 'towards_target', 'away_from_target', or 'stable'
    
    if current_deviation < previous_deviation * 0.9:
        return "towards_target"  # Getting better
    elif current_deviation > previous_deviation * 1.1:
        return "away_from_target"  # Getting worse
    else:
        return "stable"  # No significant change

Trend-based Adjustments:

Trend Stage 1 Threshold Stage 2 Threshold Behavior
Towards Target 60% of deadband 80% of deadband More aggressive, enter earlier
Stable 80% of deadband 90% of deadband Normal thresholds
Away from Target 90% of deadband 95% of deadband Conservative, enter later

Example:

  • VPD deviation: 0.03 kPa
  • Deadband: 0.05 kPa
  • Trend: towards_target
  • Result: Enter Stage 1 at 0.03 kPa (60% threshold) instead of 0.04 kPa (80% threshold)

Night Mode Behavior with Hysteresis

The Smart Deadband behavior changes based on is_light_on and nightVPDHold settings:

is_night = not is_light_on
night_vpd_hold = controlOptions.nightVPDHold

Behavior Matrix:

Light Status NightHoldVPD Deadband Behavior Device Behavior
ON Any ✅ Active with hysteresis Normal VPD control
OFF True ✅ Active with hysteresis Normal VPD control at night
OFF False ❌ Inactive (blocked) Power-saving mode only

Power-Saving Mode (Light OFF + NightHoldVPD=False):

if is_night and not night_vpd_hold:
    # Deadband is NOT active
    # Night Hold Fallback is used instead
    
    # Climate Devices (Minimized to save power):
    • canHeat, canCool, canHumidify, canDehumidify → Reduce (OFF)
    • canClimate, canCO2, canLight → Reduce (OFF)
    
    # Ventilation Devices (Active for mold prevention):
    • canExhaust → Increase (Air exchange!)
    • canVentilate → Increase (Air circulation!)
    • canWindow → Increase (Air exchange!)
    • canIntake → Variable (based on outside temp)

Why this behavior?

  • Night with NightHoldVPD=True: User wants VPD control at night → Deadband runs with hysteresis
  • Night with NightHoldVPD=False: Power-saving priority → No deadband, only active ventilation for mold prevention

Hysteresis for Oscillation Prevention (NEW!)

The Smart Deadband now includes 15% hysteresis to prevent oscillation at deadband boundaries:

# Configuration
hysteresis_factor = 1.15  # 15% hysteresis
min_hold_after_exit = 120  # Max 2 minutes hold after exit

How Hysteresis Works:

Example: Deadband = ±0.05 kPa, Target = 1.10 kPa

Entry Condition:
  deviation <= deadband (e.g., VPD=1.08 → |1.08-1.10| = 0.02 ≤ 0.05 ✅)
  → Enters deadband
  
Exit Condition (WITH Hysteresis):
  deviation > exit_threshold (e.g., VPD=1.16 → |1.16-1.10| = 0.06 > 0.0575 ✅)
  → Exits deadband

  where exit_threshold = deadband * 1.15 = 0.05 * 1.15 = 0.0575
  
Boundary Oscillation Example:
  VPD: 1.049 → deviation=0.051 > 0.0575? NO ✅ → Still in deadband
  VPD: 1.050 → deviation=0.050 > 0.0575? NO ✅ → Still in deadband
  VPD: 1.051 → deviation=0.049 > 0.0575? NO ✅ → Still in deadband
  
  → NO OSCILLATION even with slight fluctuations!

Re-Entry Block after Exit:

# After exiting deadband, wait minimum 120s before re-entering
if _deadband_last_exit_time:
    time_since_exit = now - _deadband_last_exit_time
    if time_since_exit < 120:  # 2 minutes
        return  # Block re-entry

Benefits of Hysteresis:

  • ✅ Stability: Prevents constant entering/exiting at boundaries
  • ✅ Reduced Device Wear: Fewer device state changes
  • ✅ Smoother Operation: Gradual transitions instead of rapid toggling
  • ✅ Better Energy Efficiency: Devices stay in optimal state longer

Logging (INFO Level + LogForClient):

{
  "Name": "Room1",
  "message": "Smart Deadband Stage 2 active - hold: 120s, trend: stable",
  "VPDStatus": "InDeadband",
  "currentVPD": 1.10,
  "targetVPD": 1.10,
  "deadband": 0.05,
  "exitThreshold": 0.0575,
  "deviation": 0.00,
  "holdTimeRemaining": 120,
  "holdDuration": 300,
  "stage": 2,
  "trend": "stable",
  "mode": "VPD Perfection",
  "hysteresisFactor": 1.15,
  "deadbandActive": true
}

Maximum Deadband Time with Periodic Checks

# Configuration
max_deadband_time = 600 seconds  # 10 minutes
deadband_check_interval = 30 seconds  # Check every 30 seconds
deadband_hold_duration = 300 seconds  # 5 minutes hold time
hysteresis_factor = 1.15  # 15% hysteresis for exit
min_hold_after_exit = 120  # Max 2 minutes hold after exit

Behavior:

  1. Max Time (10 min): After 10 minutes in deadband, automatically exit
  2. Periodic Checks (30 sec): Every 30 seconds, check if VPD still stable
  3. Auto-Extension: If VPD stable and trending towards target, extend for another 5 minutes
  4. Early Exit with Hysteresis: If deviation > deadband * 1.15, exit immediately (prevents oscillation)
  5. Re-Entry Block: Minimum 120 seconds wait time after exit before re-entering deadband

Implementation Details

_handle_smart_deadband() (OGBModeManager.py) - Updated with Return Value:

async def _handle_smart_deadband(
    self, current_vpd: float, target_vpd: float, deadband: float, mode_name: str
) -> bool:
    """
    Smart Deadband Handler - Advanced version with dynamic stages and predictive logic.

    Returns:
        bool: True if deadband is active, False if deadband is blocked
              (e.g., night mode without nightVPDHold)
    """
    # ... deadband logic ...

    if is_night and not night_vpd_hold:
        # Night mode without VPD hold - no deadband
        if self._is_in_deadband:
            self._reset_deadband_state()
        return False  # Deadband is NOT active

    # ... deadband logic ...

    # Fixed Hold Time Extension Logic:
    # Extend only if trend is good AND within hysteresis zone
    if hold_remaining <= 0:
        if trend == "stable" or trend == "towards_target":
            if deviation <= self._deadband_exit_threshold:
                # Both conditions met: stable trend AND within hysteresis zone
                self._deadband_hold_start = now
                _LOGGER.debug("Extending deadband - VPD stable and within hysteresis zone")
            else:
                # Trend is good but outside hysteresis zone - exit
                self._reset_deadband_state()
                return False
        else:
            # Trend is bad - exit
            self._reset_deadband_state()
            return False

    return True  # Deadband IS active

Device State Restoration (Device.py):

async def on_smart_deadband_entered(self, data) -> None:
    """Save current state before entering deadband."""
    if self.isDimmable:
        self._pre_deadband_duty_cycle = self.dutyCycle
    else:
        self._pre_deadband_is_running = self.isRunning

    await self.setToMinimum()
    self._in_smart_deadband = True

async def on_smart_deadband_exited(self, data) -> None:
    """Restore previous state when exiting deadband."""
    if self._in_smart_deadband:
        self._in_smart_deadband = False
        await self.restoreFromMinimum()

async def restoreFromMinimum(self):
    """Restore device to previous state before entering deadband."""
    if self.isDimmable:
        if self._pre_deadband_duty_cycle is not None:
            clamped = self.clamp_duty_cycle(self._pre_deadband_duty_cycle)
            await self.turn_on(percentage=clamped)
    else:
        if self._pre_deadband_is_running is not None:
            if self._pre_deadband_is_running:
                await self.turn_on()
            else:
                await self.turn_off()

_calculate_dynamic_deadband() (OGBModeManager.py):

def _calculate_dynamic_deadband(self, mode_name: str) -> float:
    """Calculate dynamic deadband based on plant stage and mode."""
    
    if mode_name == "VPD Perfection":
        plant_stage = self.data_store.get("plantStage") or "MidVeg"
        stage_deadbands = {
            "Germination": 0.03,
            "Clones": 0.03,
            "EarlyVeg": 0.05,
            "MidVeg": 0.05,
            "LateVeg": 0.04,
            "EarlyFlower": 0.04,
            "MidFlower": 0.05,
            "LateFlower": 0.05,
        }
        return stage_deadbands.get(plant_stage, 0.05)
        
    elif mode_name == "VPD Target":
        # Use tolerance from settings
        tolerance = self.data_store.getDeep("controlOptionData.deadband.vpdTargetDeadband")
        return float(tolerance) if tolerance else 0.05
        
    elif mode_name == "Closed Environment":
        return 0.05  # Fixed deadband

_determine_deadband_stage() (OGBModeManager.py):

def _determine_deadband_stage(self, deviation: float, deadband: float, trend: str) -> int:
    """Determine reduction stage based on deviation and trend."""
    
    relative_deviation = deviation / deadband
    
    # Trend-based thresholds
    if trend == "towards_target":
        stage_1_threshold = 0.60  # 60%
        stage_2_threshold = 0.80  # 80%
    elif trend == "away_from_target":
        stage_1_threshold = 0.90  # 90%
        stage_2_threshold = 0.95  # 95%
    else:
        stage_1_threshold = 0.80  # 80%
        stage_2_threshold = 0.90  # 90%
    
    # Determine stage
    if relative_deviation < stage_1_threshold:
        return 1  # Soft
    elif relative_deviation < stage_2_threshold:
        return 2  # Medium
    elif stability_duration >= 120:  # 2 minutes stable
        return 3  # Full
    else:
        return 2  # Stay at medium

Log Output Example

{
  "Name": "Room1",
  "message": "Smart Deadband Stage 2 active - hold: 245s, trend: towards_target",
  "VPDStatus": "InDeadband",
  "currentVPD": 1.23,
  "targetVPD": 1.20,
  "deadband": 0.05,
  "deviation": 0.03,
  "holdTimeRemaining": 245,
  "holdDuration": 300,
  "stage": 2,
  "trend": "towards_target",
  "mode": "VPD Perfection",
  "devicesDimmed": ["canCool:25%", "canExhaust:50%"],
  "devicesReduced": [],
  "ventilationRunning": ["canVentilate"],
  "lightStatus": "running (unchanged)",
  "deadbandActive": true
}

Summary of Smart Deadband Features

Feature Before After
Deadband Size Fixed 0.05 kPa Dynamic based on plant stage
Reduction Immediate to 10% 3-stage gradual (50% → 25% → 10%)
Trend Analysis None Last 3 VPD values analyzed
Night Mode Always active Only with nightVPDHold
Max Time 2.5 minutes 10 minutes with 30s checks
Extension Automatic Only if stable/towards_target
Exit Threshold Immediate at deadband 15% hysteresis (deadband * 1.15)
Re-Entry Block None Minimum 120 seconds after exit

Deadband & Quiet Zone

Overview

The Smart Deadband is a sophisticated feature that reduces device activity when VPD is within an acceptable range, providing:

  • Energy Savings: Devices run at minimum (10%-25%-50%)
  • Reduced Wear: Fewer device state changes
  • Oscillation Prevention: 15% hysteresis prevents boundary oscillation
  • Stability Tracking: Trend analysis and periodic checks

How It Works

┌─────────────────────────────────────────────────────────────────────┐
│ DEADBAND FLOW DIAGRAM                                              │
├─────────────────────────────────────────────────────────────────────┤
│                                                                     │
│  VPD Reading → Calculate Deviation → Check Deadband                │
│                                                                     │
│  IF deviation <= deadband (e.g., 0.05 kPa):                       │
│    ├─ Check night mode + nightVPDHold                             │
│    │  ├─ Light OFF + nightVPDHold=False → RETURN False (blocked) │
│    │  └─ Light ON OR nightVPDHold=True → CONTINUE                 │
│    │                                                               │
│    ├─ Check if already in deadband                               │
│    │  ├─ NO → Enter deadband (set flag, emit events)            │
│    │  └─ YES → Continue (skip entry)                             │
│    │                                                               │
│    ├─ Check time since exit (re-entry block)                      │
│    │  └─ < 120s → RETURN False (block re-entry)                  │
│    │                                                               │
│    ├─ Determine stage (based on deviation + trend)                │
│    │  ├─ Stage 1 (Soft): Climate 50%, Air 75%                   │
│    │  ├─ Stage 2 (Medium): Climate 25%, Air 50%                 │
│    │  └─ Stage 3 (Full): Climate 10%, Air 25%                   │
│    │                                                               │
│    ├─ Emit SmartDeadbandEntered events                            │
│    ├─ Reduce devices according to stage                           │
│    ├─ Emit LogForClient (INFO + hysteresis info)                  │
│    └─ RETURN True (deadband active)                               │
│                                                                     │
│  ELIF deviation > exit_threshold (deadband * 1.15):                │
│    ├─ Exit deadband                                                │
│    ├─ Record exit time (for re-entry block)                       │
│    ├─ Emit SmartDeadbandExited events                             │
│    ├─ Reset all deadband state                                    │
│    └─ RETURN False (deadband not active)                          │
│                                                                     │
│  ELSE:                                                             │
│    ├─ Continue normal operation                                    │
│    └─ Process VPD actions (increase/reduce)                       │
│                                                                     │
└─────────────────────────────────────────────────────────────────────┘

🆕 NEW: _handle_smart_deadband() now returns bool:
     • True  → Deadband is active (devices reduced)
     • False → Deadband is NOT active (blocked, e.g., night mode)

Deadband vs Quiet Zone

Aspect Smart Deadband Quiet Zone
Purpose Reduce device activity when VPD is good Pause all VPD control temporarily
Trigger VPD within ±deadband of target VPD in deadband AND quiet zone active
Duration Up to 10 minutes (extendable) Until conditions change
Device State Reduced (10%-25%-50%) Paused
Events SmartDeadbandEntered/Exited Quiet Zone signal
Log Level INFO (with hysteresis info) INFO (devices paused)

Example Scenarios

Scenario 1: Perfect VPD (Deadband Active)

VPD = 1.10, Target = 1.10, Deadband = ±0.05
Deviation = 0.00 ≤ 0.05 → IN DEADBAND

Stage 3 (Full): Stable 2+ minutes
- Heater: 10% (reduced from 80%)
- Cooler: 10% (reduced from 60%)
- Exhaust: 25% (reduced from 70%)
- Ventilation: 100% (unchanged)

Log: "Smart Deadband Stage 3 active - hold: 120s, trend: stable"

Scenario 2: Boundary Oscillation (Hysteresis Prevents Chaos)

VPD oscillates: 1.049, 1.050, 1.051, 1.050, 1.049
Target = 1.10, Deadband = ±0.05, Exit Threshold = 0.0575

Cycle 1: VPD=1.049, deviation=0.051, exit_threshold=0.0575
  → 0.051 > 0.0575? NO → STAYS IN DEADBAND

Cycle 2: VPD=1.050, deviation=0.050, exit_threshold=0.0575
  → 0.050 > 0.0575? NO → STAYS IN DEADBAND

Cycle 3: VPD=1.051, deviation=0.049, exit_threshold=0.0575
  → 0.049 > 0.0575? NO → STAYS IN DEADBAND

Result: NO OSCILLATION, devices remain reduced!

Scenario 3: Night Mode with NightHoldVPD=True

Light: OFF, NightHoldVPD: TRUE
VPD = 1.08, Target = 1.10, Deadband = ±0.05
Deviation = 0.02 ≤ 0.05 → DEADBAND ACTIVE WITH HYSTERESIS

Deadband runs normally at night:
- Climate devices reduced to 10%-25%-50%
- Air exchange devices reduced
- Ventilation continues for air circulation
- Hold time: 2.5 minutes
- Exit threshold: 0.0575 (15% hysteresis)

Log: "Night mode WITH NightHoldVPD - deadband active with hysteresis"

Scenario 4: Night Mode with NightHoldVPD=False

Light: OFF, NightHoldVPD: FALSE
VPD = 1.08, Target = 1.10

DEADBAND IS NOT ACTIVE (blocked by night mode)

Night Hold Power-Saving Mode:
- Climate devices: Reduce (OFF) - save power
- Ventilation devices: Increase - mold prevention!
  • Exhaust: Increase (air exchange)
  • Ventilate: Increase (air circulation)
  • Window: Increase (air exchange)
  • Intake: Variable (based on outside temp)

Log: "Night Hold Power-Saving Mode - Climate minimized, Ventilation active"

Configuration Parameters

Parameter Default Description
deadband 0.05 kPa Base deadband value (varies by plant stage)
hysteresis_factor 1.15 (15%) Exit threshold = deadband × 1.15
min_hold_after_exit 120 seconds Minimum wait time before re-entry
max_deadband_time 600 seconds (10 min) Maximum time in deadband
deadband_check_interval 30 seconds Check interval during deadband
deadband_hold_duration 300 seconds (5 min) Base hold time

Logging

Deadband Entry (INFO):

{
  "Name": "Room1",
  "message": "VPD 1.10 entered deadband ±0.05 of target 1.10 - starting smart deadband (hold: 300s)",
  "currentVPD": 1.10,
  "targetVPD": 1.10,
  "deadband": 0.05,
  "exitThreshold": 0.0575,
  "hysteresisFactor": 1.15,
  "mode": "VPD Perfection"
}

Deadband Exit (INFO):

{
  "Name": "Room1",
  "message": "VPD 1.16 EXITED deadband with hysteresis (deviation: 0.06 > exit_threshold: 0.0575, deadband: 0.05, last_exit: 0s ago) - exiting deadband"
}

Deadband Active (INFO - Every 30s):

{
  "Name": "Room1",
  "message": "Smart Deadband Stage 2 active - hold: 120s, trend: stable",
  "VPDStatus": "InDeadband",
  "currentVPD": 1.10,
  "targetVPD": 1.10,
  "deadband": 0.05,
  "exitThreshold": 0.0575,
  "deviation": 0.00,
  "holdTimeRemaining": 120,
  "holdDuration": 300,
  "stage": 2,
  "trend": "stable",
  "mode": "VPD Perfection",
  "hysteresisFactor": 1.15,
  "deadbandActive": true,
  "devicesDimmed": ["canHeat:25%", "canCool:25%"],
  "devicesReduced": ["canHumidify", "canDehumidify"],
  "ventilationRunning": ["canVentilate"]
}

Closed Environment Night Mode Power-Saving

Overview

Closed Environment Mode now includes Night Mode Power-Saving functionality, which is activated when:

  • Light is OFF (isPlantDay.islightON = False)
  • AND nightVPDHold = False

Power-Saving Logic

When Night Mode Power-Saving is active, the system optimizes for energy efficiency while maintaining mold prevention:

┌─────────────────────────────────────────────────────────────────────────────┐
│ NIGHT MODE POWER-SAVING FOR CLOSED ENVIRONMENT                              │
├─────────────────────────────────────────────────────────────────────────────┤
│                                                                             │
│ Climate Devices (Minimized to Save Power):                                  │
│ • canHeat       → Reduce (Heater OFF)                                      │
│ • canCool       → Reduce (Cooler OFF)                                      │
│ • canHumidify   → Reduce (Humidifier OFF)                                  │
│ • canDehumidify→ Reduce (Dehumidifier OFF)                                │
│ • canClimate    → Reduce (Climate OFF)                                     │
│ • canCO2        → Reduce (CO2 OFF)                                         │
│ • canLight      → Reduce (Light OFF)                                       │
│                                                                             │
│ Ventilation Devices (Active for Mold Prevention):                           │
│ • canExhaust    → Increase (Air exchange!)                                 │
│ • canVentilate  → Increase (Air circulation!)                              │
│ • canWindow     → Increase (Air exchange!)                                 │
│ • canIntake     → Variable (based on outside temperature)                   │
│                                                                             │
│ Intake Logic:                                                              │
│ IF outside_temp >= (minTemp - 3°C):                                         │
│    → Increase (Outside air is warm enough)                                 │
│ ELSE:                                                                      │
│    → Reduce (Too cold, save heating)                                       │
│                                                                             │
│ ⚠️ IMPORTANT: VPD is NOT used for control in Closed Environment!           │
│ • VPD is only used for Smart Deadband check                                 │
│ • Temperature and Humidity use their OWN targets                            │
│ • VPD in log is for informational purposes only                             │
│                                                                             │
└─────────────────────────────────────────────────────────────────────────────┘

Example Log Output (Night Mode Power-Saving)

{
  "Name": "dev_room",
  "message": "Night Mode Power-Saving: Climate minimized, Ventilation active - 8 actions",
  "actions": "canHeat:Reduce, canCool:Reduce, canHumidify:Reduce, canDehumidify:Reduce, canClimate:Reduce, canCO2:Reduce, canExhaust:Increase, canVentilate:Increase",
  "actionCount": 8,
  "tempCurrent": 18.5,
  "humCurrent": 65.0,
  "co2Current": 600,
  "vpdCurrent": 0.65,
  "isNightMode": true,
  "nightVPDHold": false
}

Key Differences to VPD Perfection/Target Night Mode

Aspect VPD Perfection/Target Closed Environment
Night Mode Trigger is_light_on = False AND nightVPDHold = False Same
Climate Devices Reduced/Minimized Reduced (OFF)
VPD Control Paused (no VPD actions) N/A (no VPD control)
Temp/Hum Control Paused Uses tentData min/max limits (for display: midpoint of min/max)
Ventilation Active (mold prevention) Active (mold prevention)
VPD in Log vpdCurrent, vpdTarget, vpdDeviation, vpdStatus vpdCurrent (informational only)
Control Logic VPD-based control paused Control based on tentData min/max limits

Recent Bug Fixes and Improvements

Bug Fixes (2026-04-07)

1. ✅ Fixed: Hold Time Extension Logic (OGBModeManager.py:518-537)

Problem: When hold time elapsed and trend was "away_from_target", the deadband state was reset then immediately extended, causing inconsistent behavior.

Fix: Modified the hold time extension logic to only extend when BOTH conditions are met:

  • Trend is good ("stable" OR "towards_target")
  • AND VPD is within hysteresis zone (deviation <= exit_threshold)

Before:

if hold_remaining <= 0:
    if trend == "stable" or trend == "towards_target":
        self._deadband_hold_start = now  # Extend
    else:
        self._reset_deadband_state()  # Reset
    if deviation <= self._deadband_exit_threshold:
        self._deadband_hold_start = now  # CONFLICT: Reset then extended!

After:

if hold_remaining <= 0:
    if trend == "stable" or trend == "towards_target":
        if deviation <= self._deadband_exit_threshold:
            # Both conditions met: extend
            self._deadband_hold_start = now
        else:
            # Trend is good but outside hysteresis zone: exit
            self._reset_deadband_state()
            return False
    else:
        # Trend is bad: exit
        self._reset_deadband_state()
        return False

2. ✅ Fixed: Device State Not Restored on Exit (Device.py:2592-2612)

Problem: When devices exited deadband, they only set _in_smart_deadband = False but did NOT restore their previous state, potentially leaving devices at minimum for an extended period.

Fix: Implemented state saving and restoration:

  1. Save current state (_pre_deadband_duty_cycle or _pre_deadband_is_running) before entering deadband
  2. Restore previous state when exiting deadband via restoreFromMinimum()

Changes:

  • Added _pre_deadband_duty_cycle and _pre_deadband_is_running attributes
  • Modified on_smart_deadband_entered() to save current state
  • Added restoreFromMinimum() method to restore previous state
  • Modified on_smart_deadband_exited() to call restoreFromMinimum()

3. ✅ Removed: Redundant "Reduce" Events (OGBModeManager.py:494-516)

Problem: Deadband handler emitted "Reduce" events for devices, but these were immediately blocked by device handlers because _in_smart_deadband was already True. This was inefficient and unnecessary.

Fix: Removed the redundant "Reduce" event emission (lines 494-516). The SmartDeadbandEntered event already handles device reduction via setToMinimum().

Impact: Reduced event traffic and improved efficiency.

CO2 Control Behavior (Design Decision)

The CO2 control behavior is intentionally different across modes:

Mode CO2 in Deadband CO2 outside Deadband Reasoning
VPD Perfection ❌ No ✅ Yes Optimize for energy when VPD is already in target zone
Closed Environment ✅ Yes ✅ Yes CO2 is critical for sealed chambers, maintain even in deadband
VPD Target ❌ No ❌ No Simpler mode focused on VPD control only

This is a design decision, not a bug. Each mode has its own optimization strategy.

Test Coverage

All fixes are covered by comprehensive tests:

  • test_deadband_hysteresis.py: 17 tests (all passing)

    • Hysteresis exit threshold
    • Night mode blocking
    • Smart Deadband return values
    • Hold time extension with good trend
  • test_closed_environment_deadband.py: 6 tests (all passing)

    • Night mode power-saving
    • Smart Deadband respect
    • Own targets vs VPD targets
    • VPD as informational only
  • test_closed_environment_manager.py: 5 tests (all passing)

    • Cycle execution
    • Target usage
    • Night mode handling
  • test_deadband_return_value.py: 6 tests (all passing)

    • Return value consistency across all modes
    • Caller usage verification

Dampening Control (Core Logic vs Dampening Features)

Concept

The system has been refactored to clearly separate Core VPD Logic from Dampening Features:

  1. Core VPD Logic (ALWAYS active for VPD Perfection and VPD Target):

    • Buffer Zones (prevent oscillation near limits)
    • VPD Context (priorities based on VPD status)
    • Deviations-based actions (intelligent additional actions)
    • Conflict resolution (resolve contradictory actions)
  2. Dampening Features (only when vpdDeviceDampening = True):

    • Cooldown filtering (user-defined base cooldowns)
    • Repeat cooldown (prevent immediate same action)
    • Emergency override (bypass cooldown in critical conditions)
  3. Closed Environment: Has its own cycle, only needs:

    • Conflict resolution
    • Environment Guard
    • Execute

IMPORTANT: Core VPD Logic is ONLY applied to VPD Perfection and VPD Target modes, NOT to Closed Environment or Premium modes (PID/MPC/AI).

Mode-Specific Behavior

Mode Core VPD Logic Dampening Features Environment Guard
VPD Perfection ✅ Active (Buffer Zones, VPD Context, Conflicts) ⚙️ Optional (if vpdDeviceDampening = True) ✅ Active
VPD Target ✅ Active (Buffer Zones, VPD Context, Conflicts) ⚙️ Optional (if vpdDeviceDampening = True) ✅ Active
Closed Environment ❌ Not used (has own logic) ❌ Not used ✅ Active
PID/MPC/AI Control ❌ Not used ❌ Not used ✅ Active
Script Mode ❌ Not used ❌ Not used ✅ Active

Configuration

"controlOptions": {
    "vpdDeviceDampening": False,  # Default: False (user-defined base cooldowns only)
    "adaptiveCooldownEnabled": False,  # Default: False (user says x, gets x)
    "emergencyCooldownFactor": 0.5,  # Default: 0.5 (50% reduction in emergency)
    "adaptiveCooldownThresholds": {  # Optional: Only if adaptiveCooldownEnabled = True
        "critical": 5.0,
        "high": 3.0,
        "near": 1.0,
        "veryNear": 0.5
    },
    "adaptiveCooldownFactors": {  # Optional: Only if adaptiveCooldownEnabled = True
        "critical": 1.5,
        "high": 1.2,
        "near": 2.0,
        "veryNear": 3.0
    }
}

Default Device Cooldowns

DEFAULT_DEVICE_COOLDOWNS = {
    "canHumidify": 5,   # Befeuchter braucht Zeit
    "canDehumidify": 3, # Entfeuchter braucht noch mehr Zeit
    "canHeat": 3,       # Heizung reagiert relativ schnell
    "canCool": 3,       # Kühlung braucht etwas Zeit
    "canExhaust": 1,    # Abluft reagiert schnell
    "canIntake": 1,     # Zuluft reagiert schnell
    "canVentilate": 1,  # Ventilation reagiert schnell
    "canWindow": 1,     # Window actuator reacts quickly
    "canDoor": 1,       # Door contact events should not spam
    "canLight": 1,      # Licht reagiert sofort, aber VPD-Effekt braucht Zeit
    "canCO2": 2,        # CO2 braucht Zeit zur Verteilung
    "canClimate": 2,    # Klima-System braucht Zeit
}

Implementation

VPD Perfection Mode (OGBActionManager.py):

async def checkLimitsAndPublicate(self, actionMap: List):
    """Process VPD Perfection actions with clean separation of Core Logic and Dampening."""
    
    # Check mode - Core VPD Logic only for VPD Perfection and VPD Target
    mode = self.data_store.get("tentMode")
    vpd_modes = {"VPD Perfection", "VPD Target"}
    is_vpd_mode = mode in vpd_modes
    
    if not is_vpd_mode:
        # For non-VPD modes (Closed Environment, PID, MPC, AI, Script)
        final_actions = await self._apply_environment_guard(actionMap)
        await self.publicationActionHandler(final_actions)
        return
    
    # Night Hold and Deadband checks
    if not await self._check_vpd_night_hold(actionMap):
        return
    
    in_deadband, reason = self._is_vpd_in_deadband()
    if in_deadband:
        await self._emit_quiet_zone_idle()
        return
    
    # Calculate deviations
    (real_temp_dev, real_hum_dev, weighted_temp_dev, weighted_hum_dev,
     tempWeight, humWeight, tempPercentage, humPercentage, weightMessage) = \
        self._calculate_weighted_deviations(tent_data)
    
    # STEP 1: CORE VPD LOGIC (ALWAYS active)
    if self.dampening_actions:
        enhanced_actions = await self.dampening_actions.process_core_vpd_logic(
            actionMap, weighted_temp_dev, weighted_hum_dev, tent_data
        )
    else:
        enhanced_actions = self._resolve_action_conflicts(actionMap)
    
    # STEP 2: DAMPENING FEATURES (only if enabled)
    dampening_enabled = self.data_store.getDeep("controlOptions.vpdDeviceDampening", False)
    blocked_actions = []
    
    if dampening_enabled and self.dampening_actions:
        filtered_actions, blocked_actions = await self.dampening_actions.process_dampening_features(
            enhanced_actions, weighted_temp_dev, weighted_hum_dev, tent_data
        )
        final_actions = self._resolve_action_conflicts(filtered_actions)
    else:
        final_actions = enhanced_actions
    
    # STEP 3: ENVIRONMENT GUARD (always active)
    final_actions = await self._apply_environment_guard(final_actions)
    
    # STEP 4: Execute actions
    await self.publicationActionHandler(final_actions)
    
    # Log results
    await self._log_vpd_results(
        real_temp_dev, real_hum_dev, tempPercentage, humPercentage,
        final_actions, blocked_actions, dampening_enabled
    )

VPD Target Mode (OGBActionManager.py):

Similar to VPD Perfection, but uses VPD deviation only (no temp/hum weighted deviations).

Closed Environment Mode (OGBActionManager.py):

async def checkLimitsAndPublicateNoVPD(self, actionMap: List):
    """
    Closed Environment: Only conflict resolution + Environment Guard.
    No Core VPD Logic (Buffer Zones, VPD Context, Deviations-based Actions).
    """
    if not actionMap:
        return
    
    # Calculate deviations for logging only
    tent_data = self.data_store.get("tentData")
    (real_temp_dev, real_hum_dev, weighted_temp_dev, weighted_hum_dev,
     tempWeight, humWeight, tempPercentage, humPercentage, weightMessage) = \
        self._calculate_weighted_deviations(tent_data)
    
    final_actions = actionMap
    
    # Only conflict resolution (no Core VPD Logic)
    if self.dampening_actions:
        final_actions = self.dampening_actions._resolve_action_conflicts(actionMap)
    
    # Environment Guard
    final_actions = await self._apply_environment_guard(final_actions)
    await self.publicationActionHandler(final_actions)

Core VPD Logic Details

process_core_vpd_logic() (OGBDampeningActions.py):

async def process_core_vpd_logic(
    self, action_map: List, temp_deviation: float, hum_deviation: float,
    tent_data: Dict[str, Any]
) -> List:
    """Process Core VPD Logic (ALWAYS active)."""

    # 1. Enhance action map
    enhanced_actions = self._enhance_action_map(
        action_map, temp_deviation, hum_deviation, tent_data, caps,
        vpd_light_control, is_light_on, optimal_devices, vpd_status
    )
    #   - Apply buffer zones (prevent oscillation near limits)
    #   - Add VPD context enhancements (priorities based on VPD status)
    #   - Add deviations-based actions (intelligent additional actions)

    # 2. Apply dynamic fan logic (temperature-aware safety filter)
    enhanced_actions = self._apply_dynamic_fan_logic(enhanced_actions, tent_data)
    #   - Rewrites exhaust/intake/ventilation actions when temperature
    #     priorities conflict with static VPD fan logic
    #   - Prevents critical situations when only one fan type is available

    # 3. Resolve conflicts
    final_actions = self._resolve_action_conflicts(enhanced_actions)
    #   - Remove contradictory actions
    #   - Keep highest priority action per capability

    return final_actions

Dampening Features Details

process_dampening_features() (OGBDampeningActions.py):

async def process_dampening_features(
    self, action_map: List, temp_deviation: float, hum_deviation: float,
    tent_data: Dict[str, Any]
) -> Tuple[List, List]:
    """Process Dampening Features (only when vpdDeviceDampening = True)."""
    
    # 1. Check emergency conditions
    emergency_conditions = self.action_manager._getEmergencyOverride(tent_data)
    if emergency_conditions:
        self.action_manager._clearCooldownForEmergency(emergency_conditions)
    
    # 2. Apply cooldown filtering
    dampened_actions, blocked_actions = (
        self.action_manager._filterActionsByDampening(
            action_map, temp_deviation, hum_deviation
        )
    )
    #   - Check if device is in cooldown
    #   - Check if same action is repeating too quickly
    #   - Apply user-defined base cooldowns
    
    # 3. Resolve conflicts
    final_actions = self._resolve_action_conflicts(dampened_actions)
    
    return final_actions, blocked_actions

Adaptive Cooldown Behavior

Default (adaptiveCooldownEnabled = False):

def _calculateAdaptiveCooldown(self, capability: str, deviation: float) -> float:
    baseCooldown = self.defaultCooldownMinutes.get(capability, 2)
    
    # Check if adaptive cooldown is enabled
    adaptive_enabled = self.data_store.getDeep("controlOptions.adaptiveCooldownEnabled", False)
    if not adaptive_enabled:
        # User says x, user gets x!
        if self._emergency_mode:
            # In emergency: Reduce cooldown for faster response
            emergency_factor = self.data_store.getDeep("controlOptions.emergencyCooldownFactor", 0.5)
            return baseCooldown * emergency_factor
        return baseCooldown
    
    # Adaptive cooldown is enabled - apply factors
    # (only if user explicitly enabled this feature)
    ...

Key Points:

  • Default: adaptiveCooldownEnabled = False
  • Normal mode: User says 3 minutes, gets 3 minutes
  • Emergency mode: Cooldown reduced by 50% for faster response
  • Optional adaptive: User can enable adaptive cooldown with configurable thresholds and factors

Log Differences

With Dampening (vpdDeviceDampening = True):

{
  "Name": "Room1",
  "message": "VPD Perfection: Core Logic + Dampening: 5 actions executed (2 blocked by cooldown)",
  "actions": "canExhaust:Increase, canCool:Reduce, canDehumidify:Increase",
  "actionCount": 5,
  "blockedActions": 2,
  "dampeningEnabled": true,
  "tempDeviation": 1.6,
  "humDeviation": 0.8,
  "tempPercentage": 40.0,
  "humPercentage": 5.7,
  "vpdStatus": "medium"
}

Without Dampening (vpdDeviceDampening = False):

{
  "Name": "Room1",
  "message": "VPD Perfection: Core Logic only (dampening disabled): 7 actions executed",
  "actions": "canExhaust:Increase, canCool:Reduce, canHumidify:Increase, canDehumidify:Increase",
  "actionCount": 7,
  "blockedActions": 0,
  "dampeningEnabled": false,
  "tempDeviation": 1.6,
  "humDeviation": 0.8,
  "tempPercentage": 40.0,
  "humPercentage": 5.7
}

Summary of Changes

Before Refactor:

  • vpdDeviceDampening = False → NO Core VPD Logic, NO Dampening → Oszillation possible
  • vpdDeviceDampening = True → Everything (Core VPD Logic + Dampening)
  • Adaptive Cooldown was always active (hardcoded)

After Refactor:

  • Core VPD Logic (Buffer Zones, VPD Context, Conflicts) → ALWAYS active for VPD Perfection and VPD Target
  • Dampening Features (Cooldown, Emergency Override) → ONLY if vpdDeviceDampening = True
  • Adaptive Cooldown → Disabled by default (user says x, gets x)
  • Closed Environment → Uses only Conflict Resolution + Environment Guard (no Core VPD Logic)
  • Premium Modes (PID/MPC/AI) → No Core VPD Logic