Validation Matrix

Use this matrix when evaluating ARServer on a lab bench, FAT bench, or simulated environment.

Area What to validate Expected result
Application start Portable package opens on Windows Main workspace loads without Visual Studio
Mock mode Add sample IED and select signals Values update and can be mapped
IED connection Connect to test relay on MMS port Connection status and discovery are visible
SCL import Import CID/SCD/SCL file SCADA-ready signals appear in wizard
IEC Reference visibility Open signal selection wizard IEC Reference is visible near the Signal column
Modbus map Bind selected values to addresses No overlapping addresses for active points
Modbus read Read from external Modbus master Values match ARServer runtime cache
Float32 handling Read analog values from HMI Word order and scale are correct
MQTT publish Subscribe to configured topics Value, quality, status, and state topics update
Fast CB Enable Fast CB with few status points Status points are prioritized before analog points
Stale handling Disconnect IED during runtime Quality/stale indication changes visibly
Restart behavior Save project, close, reopen IED workspace and mappings are preserved
Safety Attempt Modbus write Write is rejected by design

Bench recommendation

Start with a small selected set:

  • one breaker position;
  • one trip/start flag;
  • one analog measurement;
  • one quality/status point.

Then increase point count gradually while watching refresh behavior, stale indication, and CPU/network load.