Notifications
You must be signed in to change notification settings - Fork 1
Expand file tree
/
Copy pathwall-assemblies.json
More file actions
332 lines (332 loc) · 28.4 KB
/
Copy pathwall-assemblies.json
File metadata and controls
332 lines (332 loc) · 28.4 KB
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
{
"version": "2026-08-14",
"codeEdition": "2021 IRC (citations keyed to 2021 numbering; 2015/2018 aliases in editionNotes)",
"disclaimer": "Drafting aid, not engineering. Typical/approximate values — verify with the local authority having jurisdiction (AHJ). thicknessIn values are render/BOM thicknesses; films (WRB, vapor retarder) are symbolic.",
"research": "docs/research/wall-assemblies.md",
"interior": {
"description": "Interior partition: gypsum both faces, no WRB/sheathing/cladding. Total 4.5 in on 2x4.",
"totalThicknessIn": 4.5,
"layers": [
{ "role": "drywall", "thicknessIn": 0.5, "material": "gypsum board", "citation": "2021 IRC R702.3.5 + Table R702.3.5 (1/2 in walls, either direction, studs <= 24 in o.c.)" },
{ "role": "framing", "thicknessIn": 3.5, "material": "2x4 studs @ 16 in o.c. (24 in max)", "citation": "2021 IRC R602.3 / Table R602.3(5)" },
{ "role": "drywall", "thicknessIn": 0.5, "material": "gypsum board", "citation": "2021 IRC R702.3.5 + Table R702.3.5" }
],
"gypsumThicknessOptionsIn": [0.5, 0.625],
"gypsum375Rule": { "thicknessIn": 0.375, "maxStudSpacingIn": 16, "prohibited": "under water-based texture; may not support insulation (ceilings)", "citation": "2021 IRC Table R702.3.5 + footnote d" },
"fasteners": { "nailsOcIn": 8, "screwsOcIn": 12, "screwsOcMaxIn": 16, "note": "takeoff metadata (LOD 500), not geometry", "citation": "2021 IRC Table R702.3.5" },
"ceilingBoard": {
"halfInchAnyOrientationMaxSpacingIn": 16,
"halfInchPerpendicularOnlyAtSpacingIn": 24,
"texturedAt24oc": "5/8 in or sag-resistant 1/2 in",
"citation": "2021 IRC Table R702.3.5 ceiling rows + footnote d"
}
},
"garageSeparation": {
"description": "Dwelling-garage separation. A separation, NOT a rated assembly — no fire-resistance rating is prescribed. Min 1/2 in gypsum applied to the GARAGE SIDE; Type X only on ceilings below habitable rooms.",
"totalThicknessIn": 4.5,
"layers": [
{ "role": "drywall", "thicknessIn": 0.5, "material": "gypsum board (house side, normal interior finish)", "citation": "2021 IRC R702.3.5" },
{ "role": "framing", "thicknessIn": 3.5, "material": "2x4 studs @ 16 in o.c.", "citation": "2021 IRC R602.3" },
{ "role": "drywall", "thicknessIn": 0.5, "material": "gypsum board, regular (garage side), fireSeparation tag", "citation": "2021 IRC Table R302.6 row 'From the residence and attics' — 'Not less than 1/2-inch gypsum board or equivalent applied to the garage side'" }
],
"typeXOnWallIsAmendmentOnly": { "value": true, "note": "5/8 Type X on the wall is a local amendment / builder upgrade; code-checker must accept 12.7 mm regular as compliant", "citation": "2021 IRC Table R302.6" },
"ceilingBelowHabitable": {
"layers": [
{ "role": "ceilingDrywall", "thicknessIn": 0.625, "material": "Type X gypsum, perpendicular to framing (max 24 in o.c.)", "citation": "2021 IRC Table R302.6 row 'From habitable rooms above the garage' + Table R702.3.5 Type X row" }
],
"fasteners": { "spacingOcIn": 6, "type": "1-7/8 in 6d coated nails or equivalent drywall screws", "citation": "2021 IRC Table R702.3.5" },
"penetrationSealTag": { "value": "R302.11 item 4", "citation": "2021 IRC R302.11(4)" }
},
"supportingStructure": {
"layers": [
{ "role": "drywall", "thicknessIn": 0.5, "material": "gypsum board on walls/beams/columns supporting the separation floor-ceiling", "citation": "2021 IRC Table R302.6 row 'Structure(s) supporting floor/ceiling assemblies used for separation'" }
]
},
"detachedGarageWithin3Ft": {
"maxGapFt": 3,
"layers": [
{ "role": "drywall", "thicknessIn": 0.5, "material": "gypsum board, interior side of exterior walls facing the gap", "citation": "2021 IRC Table R302.6 row 'Garages located less than 3 feet from a dwelling unit on the same lot'" }
]
},
"openings": {
"noDoorToSleepingRoom": true,
"doorOptions": ["1-3/8 in solid wood", "1-3/8 in solid or honeycomb-core steel", "20-minute fire-rated"],
"doorThicknessIn": 1.375,
"selfClosing": true,
"citation": "2021 IRC R302.5.1 (self-closing device reinstated 2018)"
},
"ducts": { "material": "No. 26 gage sheet steel min, no openings into the garage", "citation": "2021 IRC R302.5.2" }
},
"exterior": {
"stackOrderInsideOut": ["drywall", "vaporRetarder (note, zero thickness)", "framing+insulation", "sheathing", "foamCi (optional)", "wrb", "cladding"],
"stackOrderCitation": "2021 IRC R703.1 / R703.2 / R703.3 (WRB 'applied over studs or sheathing', always immediately behind the cladding)",
"baseLayers": [
{ "role": "drywall", "thicknessIn": 0.5, "material": "gypsum board, interior face", "citation": "2021 IRC R702.3.5 + Table R702.3.5" },
{ "role": "vaporRetarder", "thicknessIn": 0, "material": "class by climate zone (see vaporRetarderClassByZone); kraft facing on batt = Class II, no extra geometry", "citation": "2021 IRC R702.7 / Tables R702.7(1)-(2) (= 2018 R702.7 / Table R702.7.1)" },
{ "role": "insulation", "thicknessIn": 3.5, "material": "batt filling stud bays (3.5 in 2x4 / 5.5 in 2x6); R by climate zone", "citation": "2021 IRC N1102.1.3 / 2021 IECC Table R402.1.3" }
],
"sheathing": {
"layers": [
{ "role": "sheathing", "thicknessIn": 0.4375, "material": "wood structural panel (OSB/plywood), span rating 24/16 — 7/16 field default", "citation": "2021 IRC Table R602.3(3)" }
],
"minThicknessIn": { "studs16oc": 0.375, "studs24oc": 0.4375 },
"bracedWallMinIn": 0.375,
"fastening": { "nail": "8d common or equivalent", "edgeOcIn": 6, "fieldOcIn": 12, "citation": "2021 IRC Table R602.3(1) items 30-32; bracing R602.10.4 Method WSP" },
"gypsumSheathingOption": {
"layers": [
{ "role": "sheathing", "thicknessIn": 0.5, "material": "glass-mat gypsum sheathing (ASTM C1396/C1177), 1/2 or 5/8 in", "citation": "2021 IRC R702.3.5 ('attached ... in accordance with Table R602.3(1)') + Table R703.3(1) gypsum-sheathing fastener column" }
],
"notWsp": true,
"bracingRequiredElsewhere": "WSP corner panels, let-in braces, or Method GB interior gypsum",
"typicalUse": "under stucco and brick veneer"
},
"foamCi": {
"layers": [
{ "role": "foam", "thicknessIn": 1.0, "material": "XPS/polyiso/EPS continuous insulation (typ. 0.5-2.0 in; thicknessIn = ciR/5 for XPS)", "citation": "2021 IRC R703.15 + Tables R703.15.1/.2; R703.16/R703.17" }
],
"thicknessRangeIn": [0.5, 2.0],
"nonStructural": true,
"position": "between structural sheathing and WRB (or serves as WRB when faced/taped as approved system)",
"maxUnderBrickVeneerIn": 2.0,
"veneerTieBackingMinWspIn": 0.4375,
"claddingAttachment": "R703.15 fastener/furring tables (longer fasteners or 3/4 in vertical furring for heavy claddings)",
"citation": "2021 IRC R703.15 + Table R703.8.4(2) (ties through <= 2 in foam into >= 7/16 WSP)"
}
},
"wrb": {
"layers": [
{ "role": "wrb", "thicknessIn": 0.01, "material": "No. 15 asphalt felt (ASTM D226 Type 1) or approved housewrap (ASTM E2556); render 1/16 in symbolic", "citation": "2021 IRC R703.2 ('One layer of No. 15 asphalt felt ... applied over studs or sheathing of all exterior walls')" }
],
"renderThicknessIn": 0.0625,
"layerCountDefault": 1,
"laps": { "horizontalMinIn": 2, "verticalJointMinIn": 6, "installation": "horizontal, shingle-fashion, continuous to top of walls, terminated at penetrations, integrated with flashing", "citation": "2021 IRC R703.2 + R703.4" },
"takeoffLapFactor": 1.1,
"stuccoOverWoodSheathing": { "layerCount": 2, "material": "two independent Grade D paper planes (or 60-min Grade D + non-absorbing layer / drainage space)", "citation": "2021 IRC R703.7.3 (split R703.7.3.1/.2 in 2021; = 2018 R703.6.3)", "amendmentNote": "dry-southwest jurisdictions commonly amend — override point" },
"omittedWhen": [
{ "condition": "detached accessory building", "caveat": "some states (e.g. Ohio) delete this exception", "citation": "2021 IRC R703.2 Exception" },
{ "condition": "concrete/masonry walls designed per ch. 6 and flashed per R703.4/R703.8", "citation": "2021 IRC R703.1.1 Exception 1" },
{ "condition": "assembly passed ASTM E331 (6.24 psf, 2 h)", "citation": "2021 IRC R703.1.1 Exception 2" }
],
"neverSuppressByCladdingType": true,
"openingFlashing": { "edges": 4, "note": "flashing edge annotation on all RO edges; layers terminate onto each other shingle-fashion", "citation": "2021 IRC R703.4 + R703.2" }
},
"claddingAttachmentGeneral": {
"fastenerTableAssumesMaxStudSpacingIn": 16,
"maxSupportSpacingIn": 24,
"substrateColumns": ["WSP+stud", "fiberboard+stud", "gypsumSheathing+stud", "overFoam (defer R703.15)", "directToStud (several sidings not allowed)"],
"citation": "2021 IRC R703.3 + Table R703.3(1) ('Nominal material thicknesses ... based on a maximum stud spacing of 16 inches on center')"
},
"claddings": {
"vinyl": {
"layers": [
{ "role": "cladding", "thicknessIn": 0.75, "material": "vinyl siding, lap-profile bounding depth (panel skin 0.035 in min nominal / ~0.040-0.048 in actual)", "citation": "2021 IRC R703.11 + Table R703.3(1) vinyl row (ASTM D3679)" }
],
"materialMinThicknessIn": 0.035,
"vented": true,
"weightPsf": 1.5,
"fasteners": { "shankIn": 0.12, "headIn": 0.313, "penetrationIn": 1.25, "note": "nail-slot centered, not driven tight (thermal float); 16-ga staples permitted; over foam use R703.11.2 wind-adjusted attachment", "citation": "2021 IRC R703.11 + Table R703.3(1)" },
"highWindNote": "Vult >= 140 mph requires high-wind certification (VSI / ASTM D7793)",
"class3VaporCredit": true
},
"fiberCement": {
"layers": [
{ "role": "cladding", "thicknessIn": 0.3125, "material": "fiber cement lap board (ASTM C1186); effective offset 0.625 in at 1-1/4 in laps", "citation": "2021 IRC R703.10.2 + Table R703.3(1) fiber cement rows" }
],
"assemblyOffsetIn": 0.625,
"lapMinIn": 1.25,
"boardMaxWidthIn": 12,
"typicalBoardIn": 8.25,
"typicalExposureIn": 7,
"vented": false,
"weightPsf": 2.3,
"fasteners": { "type": "6d common/corrosion-resistant siding nails into studs through WSP/fiberboard/gypsum sheathing", "maxSupportOcIn": 24, "citation": "2021 IRC R703.10 + Table R703.3(1)" },
"panelVariant": { "layers": [{ "role": "cladding", "thicknessIn": 0.25, "material": "fiber cement vertical panel, joints over framing", "citation": "2021 IRC R703.10.1" }], "battens": { "thicknessIn": 0.75, "widthIn": 2.5, "citation": "2021 IRC R703.10.1" } },
"rainscreenBestPractice": { "furringIn": 0.375, "states": ["WA", "OR"], "note": "not code-mandatory" },
"class3VaporCredit": false
},
"stucco": {
"layers": [
{ "role": "cladding", "thicknessIn": 0.875, "material": "3-coat cement plaster over metal/wire lath: 3/8 scratch + 3/8 brown + 1/8 finish (ASTM C926)", "citation": "2021 IRC R703.7 (= 2018 R703.6) + Table R702.1(1)" }
],
"assemblyOffsetIn": 1.0,
"assemblyOffsetNote": "7/8 plaster + ~1/8 self-furring lath and paper layers",
"wrbLayerCount": 2,
"wrbCitation": "2021 IRC R703.7.3 (two Grade D planes over wood-based sheathing; = 2018 R703.6.3)",
"lath": { "fastenerOcIn": 6, "fastener": "1-1/2 in 11-ga nails (7/16 head) or 7/8 in 16-ga staples into framing (ASTM C1063)", "citation": "2021 IRC R703.7.1", "takeoffOnly": true },
"weepScreed": { "minGa": 26, "minThicknessIn": 0.019, "flangeMinIn": 3.5, "aboveEarthMinIn": 4, "abovePavingMinIn": 2, "location": "at or below foundation plate line; WRB layers and lath lap the flange; stucco never runs to grade", "citation": "2021 IRC R703.7.2.1 (= 2018 R703.6.1)" },
"vented": false,
"weightPsf": 10,
"flCmuVariant": { "layers": [{ "role": "cladding", "thicknessIn": 0.625, "material": "two-coat plaster direct-applied to CMU; no WRB/lath/screed (masonry substrate)", "citation": "2021 IRC R703.1.1 Exc. 1 + R703.7 two-coat-over-masonry row; FBC practice" }] },
"class3VaporCredit": false
},
"brickVeneer": {
"layers": [
{ "role": "airGap", "thicknessIn": 1.0, "material": "nominal 1 in airspace (transparent, occupies interpenetration matrix); up to 4.5 in backing-to-veneer with strand-wire/adjustable ties; grout fill alternative", "citation": "2021 IRC Table R703.8.4(1) + R703.8.4.2" },
{ "role": "veneer", "thicknessIn": 3.625, "material": "anchored brick wythe, nominal 4 in = 3-5/8 actual; veneer <= 5 in", "citation": "2021 IRC R703.8 + Table R703.3(1)" }
],
"assemblyOffsetIn": 4.625,
"vented": true,
"weightPsf": 40,
"ties": { "minSpec": "22-ga x 7/8 in corrugated or wire", "maxAreaPerTieSqft": 2.67, "maxHorizontalOcIn": 32, "maxVerticalOcIn": 24, "extraWithinOfOpeningsIn": 12, "highSeismicWindAreaPerTieSqft": 2.0, "throughFoamMaxIn": 2.0, "backingMinWspIn": 0.4375, "citation": "2021 IRC R703.8.4 / R703.8.4.1 + Table R703.8.4(2)" },
"support": { "bearsOn": "concrete/masonry foundation brick ledge — never wood framing", "brickLedgeWidenIn": 5.0, "ledgeTopBelowFinishFloorIn": [4, 8], "lintel": "steel loose angle, typ. 3-1/2 x 3-1/2 x 1/4 in at openings", "maxHeightFt": 30, "gableExtraFt": 8, "citation": "2021 IRC R703.8.2 / R703.8.2.1 + Table R703.8(1)" },
"flashingWeeps": { "flashing": "base of cavity on ledge (turned up behind WRB) + above all openings/shelf angles", "weepMinDiaIn": 0.1875, "weepMaxOcIn": 33, "location": "first course immediately above every flashing line", "citation": "2021 IRC R703.8.5 / R703.8.6" },
"brickGradeByWeathering": { "severe": "SW", "moderate": "MW-allowed", "citation": "2021 IRC R703.8.2 / ASTM C216 & C62 + Figure R301.2(3)" },
"jambReturnAddIn": 4.625,
"class3VaporCredit": true
},
"wood": {
"layers": [
{ "role": "cladding", "thicknessIn": 0.75, "material": "wood bevel lap default (bounding depth); profile minimums in minThicknessByProfileIn", "citation": "2021 IRC R703.5 + Table R703.3(1) wood siding rows" }
],
"minThicknessByProfileIn": { "rusticDrop": 0.375, "shiplapAverage": 0.59375, "bevel": 0.4375, "bevelButtTip": 0.1875, "hardboardPanel": 0.4375, "hardboardLap": 0.4375 },
"hardboardRenderIn": 0.4375,
"lapMinIn": 1.0,
"lapMinRabbetedIn": 0.5,
"fasteners": { "note": "face-nail to each bearing, penetrating framing 1-1/2 in; 1 nail per bearing to 6 in widths, 2 over 8 in; butt joints over framing", "citation": "2021 IRC R703.5 + Table R703.3(1)" },
"vented": false
},
"eifs": {
"layers": [
{ "role": "drainage", "thicknessIn": 0.25, "material": "drainage plane / vertical adhesive ribbons (>= 90% efficiency per ASTM E2273)", "citation": "2021 IRC R703.9" },
{ "role": "foam", "thicknessIn": 1.5, "material": "EPS insulation board (range 0.75-4 in)", "citation": "2021 IRC R703.9 / ASTM E2568" },
{ "role": "lamina", "thicknessIn": 0.125, "material": "reinforced base coat + finish", "citation": "2021 IRC R703.9" }
],
"assemblyOffsetIn": 2.0,
"drainageRequiredOverWoodFrame": true,
"terminationAboveGradeMinIn": 6,
"vented": false,
"weightPsf": 1.5,
"note": "barrier EIFS over wood frame is a code violation; WRB per R703.2 behind it, starter track (not weep screed)"
}
},
"defaultCladdingByState": {
"AK": "vinyl", "AL": "brickVeneer", "AR": "brickVeneer", "AZ": "stucco", "CA": "stucco",
"CO": "fiberCement", "CT": "vinyl", "DC": "vinyl", "DE": "vinyl", "FL": "stucco",
"GA": "fiberCement", "HI": "fiberCement", "IA": "vinyl", "ID": "fiberCement", "IL": "vinyl",
"IN": "vinyl", "KS": "vinyl", "KY": "vinyl", "LA": "brickVeneer", "MA": "vinyl",
"MD": "vinyl", "ME": "vinyl", "MI": "vinyl", "MN": "vinyl", "MO": "vinyl",
"MS": "brickVeneer", "MT": "fiberCement", "NC": "fiberCement", "ND": "vinyl", "NE": "vinyl",
"NH": "vinyl", "NJ": "vinyl", "NM": "stucco", "NV": "stucco", "NY": "vinyl",
"OH": "vinyl", "OK": "brickVeneer", "OR": "fiberCement", "PA": "vinyl", "RI": "vinyl",
"SC": "fiberCement", "SD": "vinyl", "TN": "brickVeneer", "TX": "brickVeneer", "UT": "stucco",
"VA": "fiberCement", "VT": "vinyl", "WA": "fiberCement", "WI": "vinyl", "WV": "vinyl",
"WY": "vinyl"
},
"defaultCladdingCitation": "Regional defaults keyed to 2021 IRC R703.6/.8/.10/.11 + data/jurisdictions-climate.json (termiteRisk, weatheringPotential, flags) and jurisdictions-adoption.json; FL default is stucco-on-CMU variant",
"insulationByClimateZone": {
"1": { "value": "R13", "compliance2021": ["R-13 cavity", "R-0 + R-10ci"], "compliance2018": ["R-13 cavity"], "studDepthIn": 3.5, "battThicknessIn": 3.5, "citation": "2021 IECC Table R402.1.3 / IRC N1102.1.3 (2018: Table R402.1.2)" },
"2": { "value": "R13", "compliance2021": ["R-13 cavity", "R-0 + R-10ci"], "compliance2018": ["R-13 cavity"], "studDepthIn": 3.5, "battThicknessIn": 3.5, "citation": "2021 IECC Table R402.1.3 / IRC N1102.1.3" },
"3": { "value": "R20", "compliance2021": ["R-20 cavity", "R-13 + R-5ci", "R-0 + R-15ci"], "compliance2018": ["R-20 cavity", "R-13 + R-5ci"], "studDepthIn": 5.5, "battThicknessIn": 5.5, "citation": "2021 IECC Table R402.1.3 / IRC N1102.1.3" },
"4": { "value": "R30", "compliance2021": ["R-30 cavity", "R-20 + R-5ci", "R-13 + R-10ci", "R-0 + R-20ci"], "compliance2018": ["R-20 cavity", "R-13 + R-5ci"], "studDepthIn": 5.5, "battThicknessIn": 5.5, "citation": "2021 IECC Table R402.1.3 (zones 4-8 unified 2021); 2018 Table R402.1.2" },
"4M": { "value": "R30", "compliance2021": ["R-30 cavity", "R-20 + R-5ci", "R-13 + R-10ci", "R-0 + R-20ci"], "compliance2018": ["R-20 cavity", "R-13 + R-5ci"], "studDepthIn": 5.5, "battThicknessIn": 5.5, "citation": "2021 IECC Table R402.1.3; Marine 4" },
"5": { "value": "R30", "compliance2021": ["R-30 cavity", "R-20 + R-5ci", "R-13 + R-10ci", "R-0 + R-20ci"], "compliance2018": ["R-20 cavity", "R-13 + R-5ci"], "studDepthIn": 5.5, "battThicknessIn": 5.5, "citation": "2021 IECC Table R402.1.3; 2018 Table R402.1.2" },
"6": { "value": "R30", "compliance2021": ["R-30 cavity", "R-20 + R-5ci", "R-13 + R-10ci", "R-0 + R-20ci"], "compliance2018": ["R-20 + R-5ci", "R-13 + R-10ci"], "studDepthIn": 5.5, "battThicknessIn": 5.5, "citation": "2021 IECC Table R402.1.3; 2018 Table R402.1.2" },
"7": { "value": "R30", "compliance2021": ["R-30 cavity", "R-20 + R-5ci", "R-13 + R-10ci", "R-0 + R-20ci"], "compliance2018": ["R-20 + R-5ci", "R-13 + R-10ci"], "compliance2009": ["R-21 cavity"], "studDepthIn": 5.5, "battThicknessIn": 5.5, "citation": "2021 IECC Table R402.1.3; 2018 Table R402.1.2" },
"8": { "value": "R30", "compliance2021": ["R-30 cavity", "R-20 + R-5ci", "R-13 + R-10ci", "R-0 + R-20ci"], "compliance2018": ["R-20 + R-5ci", "R-13 + R-10ci"], "compliance2009": ["R-21 cavity"], "studDepthIn": 5.5, "battThicknessIn": 5.5, "citation": "2021 IECC Table R402.1.3; 2018 Table R402.1.2" },
"_notes": {
"editionSelection": "pick compliance row by jurisdictions-adoption.json ircBase (>= 2021 -> compliance2021)",
"battFills": "R-13/R-15 = 3.5 in 2x4 bay; R-19/R-21/R-23 = 5.5 in 2x6 bay; 'ci' is the exterior foam layer, never cavity fill",
"ciAutoAdd": "when zone demands > R-21 cavity, add foamCi layer instead of thickening the wall",
"airTightnessACH50": { "zones0to2": 5.0, "zones3to8": 3.0, "gate": "ircBase >= 2012", "citation": "2021 IECC R402.4.1.2/.3" },
"verified": "knowledge-base (ICC/PNNL sources paywalled during session 2026-08-14)"
}
},
"vaporRetarderClassByZone": {
"1": { "required": "none", "interiorClassIProhibited": true, "interiorClassIIProhibited": true, "class3Permitted": "always", "citation": "2021 IRC Table R702.7(1) (= IBC 1404.3(1))" },
"2": { "required": "none", "interiorClassIProhibited": true, "interiorClassIIProhibited": true, "class3Permitted": "always", "citation": "2021 IRC Table R702.7(1)" },
"3": { "required": "none", "interiorClassIProhibited": true, "interiorClassIIProhibited": false, "class3Permitted": "always", "citation": "2021 IRC Table R702.7(1)" },
"4": { "required": "none (Class III suffices)", "interiorClassIProhibited": false, "interiorClassIIProhibited": false, "class3Permitted": "always", "citation": "2021 IRC R702.7 (non-marine zone 4)" },
"4M": { "required": "Class I or II", "class3PermittedIf": { "ventedCladdingOver": ["WSP", "fiberboard", "gypsum sheathing"], "ciMinR2x4": 2.5, "ciMinR2x6": 3.75 }, "citation": "2021 IRC R702.7 + Table R702.7(2) (= 2018 Table R702.7.1); verified via UpCodes IBC 1404.3 mirror" },
"5": { "required": "Class I or II", "class3PermittedIf": { "ventedCladdingOver": ["WSP", "fiberboard", "gypsum sheathing"], "ciMinR2x4": 5, "ciMinR2x6": 7.5 }, "citation": "2021 IRC R702.7 + Table R702.7(2)" },
"6": { "required": "Class I or II", "class3PermittedIf": { "ventedCladdingOver": ["fiberboard", "gypsum sheathing"], "ciMinR2x4": 7.5, "ciMinR2x6": 11.25 }, "citation": "2021 IRC R702.7 + Table R702.7(2)" },
"7": { "required": "Class I or II", "class3PermittedIf": { "ciMinR2x4": 10, "ciMinR2x6": 15 }, "citation": "2021 IRC R702.7 + Table R702.7(2)" },
"8": { "required": "Class I or II", "class3PermittedIf": { "ciMinR2x4": 12.5, "ciMinR2x6": 20 }, "citation": "2021 IRC R702.7 + Table R702.7(2)" },
"_notes": {
"classes": { "I": "poly sheet / foil, <= 0.1 perm", "II": "kraft-faced batts / smart membranes", "III": "latex or enamel paint" },
"ventedCladding": "vinyl, brick veneer with airspace, furred siding",
"resolver": "ciR >= tableMin(zone, studDepth) OR claddingVented -> Class III OK; else Class II",
"doubleVaporBarrierError": "never interior Class I when wall has low-perm exterior ci (foil/XPS >= 1 in) — any zone",
"basementExempt": "basement / below-grade walls exempt from Class I/II requirement [R702.7 exceptions]",
"verified": true
}
},
"stateClimateZone": {
"AL": "3A (2A coast)", "AK": "7 (8 interior)", "AZ": "2B (5B Flagstaff)", "AR": "3A",
"CA": "3B/3C (5B-6B mtn)", "CO": "5B (6B-7 mtn)", "CT": "5A", "DE": "4A", "DC": "4A",
"FL": "2A (1A Miami/Keys)", "GA": "3A (2A coast)", "HI": "1A", "ID": "5B (6B mtn)",
"IL": "5A (4A south)", "IN": "5A (4A south)", "IA": "5A", "KS": "4A (4B west)", "KY": "4A",
"LA": "2A (3A north)", "ME": "6A (7 north)", "MD": "4A (5A Garrett)", "MA": "5A",
"MI": "5A (6A-7 north)", "MN": "6A (7 north)", "MS": "3A (2A coast)", "MO": "4A",
"MT": "6B", "NE": "5A", "NV": "3B south (5B Reno)", "NH": "5A-6A", "NJ": "4A (5A NW)",
"NM": "4B (3B south, 5B north)", "NY": "5A (4A NYC/LI, 6A Adk)", "NC": "3A-4A (5A mtn)",
"ND": "6A-7", "OH": "5A (4A south)", "OK": "3A (4B panhandle)", "OR": "4C west (5B east)",
"PA": "5A (4A SE)", "RI": "5A", "SC": "3A (2A coast)", "SD": "5A-6A", "TN": "4A (3A west)",
"TX": "2A-3A (3B/4B west)", "UT": "5B (3B St. George)", "VT": "6A", "VA": "4A",
"WA": "4C west (5B east)", "WV": "4A-5A", "WI": "6A (5A south)", "WY": "6B (7 mtn)"
},
"stateClimateZoneCitation": "2021 IECC Figure R301.1 / county tables — dominant residential zone per state; split states (parenthesized) need a 'zone varies by county — confirm with AHJ' warning. jurisdictions-climate.json lacks an ieccZone field; overlay generator writes ieccZone + ieccZoneRange from this map.",
"overlays": {
"hvhz": {
"trigger": "flags.hvhz === true (jurisdictions-climate.json)",
"hvhzCounties": ["Miami-Dade", "Broward"],
"sheathing": { "minWspIn": 0.46875, "minWspNominal": "15/32", "nail": "8d ring-shank", "edgeSpacingIn": 6, "fieldSpacingIn": 6 },
"noaRequired": true,
"foamSheathingAsNailBase": false,
"openingProtection": "impact-rated, tested to TAS 201/202/203",
"blocksCiOnlyInsulationPath": true,
"citation": "Florida Building Code, Residential (8th Ed. 2023), HVHZ §R4402-R4412 (wood §R4409); Miami-Dade TAS 201/202/203",
"verified": "knowledge-base"
},
"wui": {
"states": { "CA": "mandatory, zone-mapped (all SRA + LRA Very High FHSZ)", "OR": "mapped-2023 (ORSC R327)", "NV": "local ordinances only", "CO": "local ordinances only", "UT": "local ordinances only" },
"standard": "CRC R337 / SFM Standard 12-7A-1 (mirrors CBC ch. 7A); §R337.7 exterior covering",
"allowedCladding": ["fiberCement", "stucco", "ignition-resistant-treated-wood", "masonry", "metal"],
"prohibitedInZone": ["vinyl", "untreated wood"],
"extent": "top of foundation to roof; vents ember-resistant",
"citation": "California Residential Code R337; Oregon ORSC R327 (2023)",
"verified": "knowledge-base"
},
"highWind": {
"trigger": "ultimateWindMph >= 130 && flags.hurricaneTies (jurisdictions-climate.json); prescriptive IRC ends at Vult >= 140",
"sheathingNailZone": { "nail": "8d ring-shank/common", "edgeSpacingIn": [4, 6], "cornerEndZoneSpacingIn": 4, "cornerEndZoneWidthFt": 4, "fullySheathed": true },
"openingProtection": "wind-borne-debris (Vult >= 130 within 1 mile of coastal MHW, or >= 140 in hurricane-prone regions)",
"claddingValidation": { "windMphThreshold": 140, "warnOn": ["vinyl", "eifs"], "prefer": ["stucco-on-CMU", "fiberCement"], "note": "no thickness change; fastener schedule + product-approval flags switch; vinyl needs VSI/ASTM D7793 rating" },
"countyLevelStates": ["AL", "GA", "LA", "MS", "NC", "SC", "TX", "VA"],
"citation": "2021 IRC R301.2.1.1/.2 + R703.1.1 + Table R301.2(1); AWC WFCM-2018; ICC 600-2020",
"verified": "knowledge-base"
},
"termite": {
"veryHeavyStates": ["FL", "LA", "HI"],
"veryHeavyRules": { "exteriorBelowGradeFoamProhibited": true, "inspectionGapIn": 6, "ciTerminatesAboveGradeIn": 6, "preferCavityPathAtGrade": true },
"heavyStates": ["AL", "AR", "CA", "GA", "MS", "NC", "OK", "SC", "TN", "TX", "VA"],
"heavyRules": { "protectionMethod": "IRC R318.1 (treated sill / soil treatment / barrier)", "sidingToGradeClearanceWarnIn": 6, "foamProhibited": false },
"citation": "2021 IRC R318.4 + Figure R301.2(6)",
"verified": "knowledge-base"
},
"weathering": {
"brickGrade": { "severe": "SW", "moderate": "MW-allowed", "negligible": "MW-allowed" },
"key": "weatheringPotential (jurisdictions-climate.json)",
"citation": "2021 IRC R703.8.2 / ASTM C216 & C62 + Figure R301.2(3)"
}
}
},
"fireblocking": {
"verticalAtCeilingAndFloor": "top/bottom plates ARE the vertical fireblocks in platform framing (tag fireblock:true)",
"horizontalMaxIntervalFt": 10,
"horizontalApplies": ["doubleStud", "staggeredStud", "furredSpaces", "balloonFramed/tallWalls crossing a floor line"],
"interfaces": "wall cavity <-> soffits/dropped/cove ceilings blocked (item 2); vents/pipes/ducts/cables sealed at ceiling+floor (item 4)",
"materials": ["2 in nominal lumber", "two 1 in thicknesses, broken laps", "23/32 in WSP backed joints", "1/2 in gypsum board", "1/4 in cement millboard", "retained mineral/glass-fiber batts"],
"capMemberOptions": [
{ "role": "fireblock", "thicknessIn": 0.5, "material": "gypsum board", "citation": "2021 IRC R302.11.1" },
{ "role": "fireblock", "thicknessIn": 1.5, "material": "2x nominal lumber", "citation": "2021 IRC R302.11.1" }
],
"citation": "2021 IRC R302.11 items 1, 2, 4 + R302.11.1"
},
"editionNotes": {
"stable2015to2021": ["R302.6", "R302.11", "R702.3.5", "R703.2", "Table R703.3(1)", "stucco", "anchored veneer"],
"renumbering2018": { "Table R703.4 (2015)": "Table R703.3(1)", "R703.6 plaster (2015)": "R703.7", "R703.7 veneer (2015)": "R703.8", "R703.6.3 / R703.6.1 (2018 stucco WRB/screed)": "R703.7.3 / R703.7.2.1 (2021)" },
"deltas2021": ["R702.7 rewritten as Tables R702.7(1)-(4) + hot-zone Class I restrictions", "IECC wall R-value bump (zones 4-5 gain ci/R-30 tier)"],
"flag2024": "2024 IRC rewrites R703.2 (WRB performance classes) — future round",
"provenance": "Verbatim values from IRC-based Ohio RC ch. 7 PDF (2018 IRC text, codes.ohio.gov 4101:8-7-01) + 2015/2018 ICC ch. 3 text; vapor tables verified via UpCodes IBC 1404.3 mirror (2026-08-14); IECC rows / HVHZ / WUI / termite from knowledge base (sources paywalled)"
}
}